Datasheet

08/04/2017 098208 - HPL-ED2017 V34.0 EN 2 / 5
Technical�data
General
Standards IEC/EN 60529
EN 50262
DIN 43656
DIN 43660
EN 60439-4 for CI...X individual enclosures with combined distribution boards from
Ci enclosures up to 680 A.
Can thus be used for socket combinations and as component for construction site
distribution boards.
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature °C -40 - +80
Ambient temperature
Mean value over 24 hours °C 35
Limit values °C
Ambient temperature limit value min. °C -5
Ambient air temperature, limit values max. °C 40
Degree of Protection IP65
Protection type IP65 (Enclosure)
IP65 (KST cable entries from below)
IP64 (KST cable entries from above)
IP00 (Cable entry open)
Power loss
Max. radiated heat dissipation with separate mounting, ambient air
temperature +20 °C
W 33
Max. radiated heat dissipation in distribution board combination to VDE 0660
Part 500
W 25
Notes When calculating the heat dissipation, the quadratic relationship of current with
the rated diversity factor a must be considered.
P
v
= I
2
x R
P
v
’ = P
v
x a
2
If no data is available concerning the load relationships of the individual circuits,
the rated diversity factor is selected conform to VDE 0660 Part 500.
additional technical data for UL-/CSA- approved devices see UL-report File No. E54120
Components Switchgear assembly components are type-tested. They are available individually
for the self-assembly of switchgear installations, distribution boards and control
panels.
Devices that can be fitted The reference values indicated in the table apply to the basic elements of the
distribution board. As far as devices, terminals etc. fitted into the enclosures are
concerned, their own specific technical data and rated values apply.
Standards
TTA - Type Tested Assemblies IEC/EN 60439-1, VDE 0660 Part 500
Low-voltage fuses IEC/EN 60269, VDE 0636
Type test VDE 0660 Part 500, IEC/EN 60439-1
Creepage and clearance distances III/3 to IEC/EN 60439-1
Flammability characteristics - Glow rod test VDE 0304 Part 3 level IIb, level IIb to IEC 60707
Regulation for the fire resistance tests of electrical products, their modules
and components, glow wire test
VDE 0471 Part 2
Operating and ambient conditions to VDE 0660 Part 500
Ambient temperature
Mean value over 24 hours °C 35
Limit values °C -5 … 40
Indoor installation
Relative humidity 90 % (at 20°C)
50% (at 40°C)
Altitude m Max. 2000
Protection type IP65 (Enclosure)
IP65 (KST cable entries from below)
IP64 (KST cable entries from above)
IP00 (Cable entry open)
Mounting grid mm 25 (DIN 43660)
Colour
Base RAL 7032, pebble grey
Housing body Transparent, colourless or RAL 7032, pebble grey
CI...-NA: Transparent cover, opaque