Datasheet

03/20/2012 HPL-ED2011 V2.0 EN (UX111) 2 / 4
Back plate:
2 x push-through diaphragm up to 11 mm
(not for CI-K2H)
Notes
Cross-referenceNumber and size of cable entries →#229310
Approbationen
UL approval No
CSA approval No
General
Standards IEC/EN 60529
DIN 43660
EN 50262
Climatic proofing Damp heat, constant to IEC 60068-2-78
Damp heat, cyclic to IEC 60068-2-30
Ambient temperature °C - 25 - 70
Ambient temperature with push-through cable entry °C - 25 … 40
Protection type Front IP65
Degree of protection with push-through cable entry IP65
Dissipatable heat loss
→Radiated heat dissipation
Material�characteristics
Material
Base, Cover Glass-fibre reinforced polycarbonate
Colour
Base RAL 9005, black (matt)
Cover Enclosure cover RAL 7035, light grey (matt)
Material�properties
Electrical
Creepage resistance to IEC 60112
Base CTI 175
Cover CTI 175
Surface resistance to IEC 60093 Ω x
10
13
1
Dielectric strength to IEC 60243-1 kV/
mm
30
Thermal
Continuous thermal stability
Enclosures °C -40 … 120
Gasket °C -40 … 80
Mechanical
IK code to EN 50102 06
max. assembly weights
per mounting rail kg 0.7
Chemical resistance
Base, Cover
Resistant Acids < 10 %, mineral oil, petrol, grease, saline solution
Partially resistant Acids > 10 %, alcohol
Not resistant Alkalis, benzol