Specification

2
Technical Data TD003006EN
Effective September 2014
Type CH (3/4-inch) dual purpose arc fault/
ground fault circuit interrupter
EATON www.eaton.com
Table 2. Specifications
Description Specification
Catalog number CHFAFGF115, CHFAFGF120, CHFAFGF115PN, CHFAFGF120PN
Voltage requirement 102 ≤ V
RMS
≤ 132
Frequency requirement 60 Hz ± 2 Hz
Power consumption 1.3 W
Surge In accordance with IEC 61000-4-5
Ambient operating
temperature
–31 °F to +150 °F (–35 °C to +66 °C)
Humidity 0% to 95%, noncondensing
Warranty Limited lifetime
ULt standards
UL 489—molded-case circuit breakers, molded-case switches,
and circuit-breaker enclosures
UL 943—ground fault circuit interrupters
UL 1699—arc fault circuit interrupters
UL 1998—software in programmable components
UL file number E-45310
Load
Power
Wire
(Black)
120 V~
Duplex Receptacle
Load Neutral
Wire (White)
Coiled White
Wire Connects to
Loadcenter Neutral
Figure 1. Type CHF Arc Fault Circuit Breaker
Load
Power
Wire
(Black)
120 V~
Duplex Receptacle
Load Neutral
Wire (White)
Neutral Clip Connects
onto the Neutral Bar
of the Panelboard to
Loadcenter Neutral
Figure 2. Type CHF Arc Fault Circuit Breaker Plug-On Neutral
Wiring diagram
Equipment Ground
120 V
Duplex
Receptacle
Neutral
Neutral
Single-Pole
120/240 V~
Source
N A B
Line B
Figure 3. Single-Pole 120 V Load Application
Sourced by 120/240 Vac