Product Brochure
Volume 5—Motor Control and Protection CA08100006E—May 2013 www.eaton.com V5-T4-87
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4.8
Definite Purpose Contactors and Starters
Ratings
Ampere Ratings of Three-Phase, 60 Hz, AC Induction Motor, continued
Notes
1
To convert horsepower to kW, multiply horsepower by 0.7457.
2
380V 50 Hz.
Syn. Speed
RPM
Current in Amperes
hp
1
200V 230V 380V
2
460V 575V 2200V
7-1/23600 22.419.511.89.797.81—
1800 24.7 21.5 13 10.7 8.55 —
1200 25.1 21.8 13.2 10.9 8.7 —
900 26.523 13.911.59.19—
10 3600 29.2 25.4 15.4 12.7 10.1 —
1800 30.8 26.8 16.3 13.4 10.7 —
1200 32.2 28 16.9 14 11.2 —
900 35.1 30.5 18.5 15.2 12.2 —
15 3600 41.9 36.4 22 18.2 14.5 —
1800 45.1 39.2 23.7 19.6 15.7 —
1200 47.6 41.4 25 20.7 16.5 —
900 51.2 44.5 26.9 22.2 17.8 —
20 3600 58 50.4 30.5 25.2 20.1 —
1800 58.9 51.2 31 25.6 20.5 —
1200 60.7 52.8 31.9 26.4 21.1 —
900 63.1 54.9 33.2 27.4 21.9 —
25 3600 69.9 60.8 36.8 30.4 24.3 —
1800 74.5 64.8 39.2 32.4 25.9 —
1200 75.4 65.6 39.6 32.8 26.2 —
900 77.4 67.3 40.7 33.7 27 —
30 3600 84.8 73.7 44.4 36.8 29.4 —
1800 86.9 75.6 45.7 37.8 30.2 —
1200 90.6 78.8 47.6 39.4 31.5 —
900 94.1 81.8 49.5 40.9 32.7 —
40 3600 111 96.4 58.2 48.2 38.5 —
1800 116 101 61 50.4 40.3 —
1200 117 102 61.2 50.6 40.4 —
900 121 105 63.2 52.2 41.7 —
50 3600 138 120 72.9 60.1 48.2 —
1800 143 124 75.2 62.2 49.7 —
1200 145 126 76.2 63 50.4 —
900 150 130 78.5 65 52 —
60 3600 164 143 86.8 71.7 57.3 —
1800 171 140 90 74.5 59.4 —
1200 173 150 91 75 60 —
900 177 154 93.1 77 61.5 —
75 3600 206 179 108 89.6 71.7 —
1800 210 183 111 91.6 73.2 —
1200 212 184 112 92 73.5 —
900 222 193 117 96.5 77.5 —