Product Brochure
V5-T4-62 Volume 5—Motor Control and Protection CA08100006E—May 2013 www.eaton.com
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4.5
Definite Purpose Contactors and Starters
Renewal Parts
DC Operation
These DC coils have separate
pick-up and seal windings.
The pick-up winding must be
connected to an early break
normally closed auxiliary
contact block and provide
the magnetic force required
to close the magnet. As the
magnet approaches the
closed position, the early
break normally closed contact
is opened and the holding coil
is inserted in series with the
pick-up winding.
The early break contact
block (C320KGD1) has to
be attached to the side of
the contactor, taking up one
of the positions available
for add-on auxiliary contact
blocks.
DC Coil Elementary Diagram—Contactors and Starters
DC Coils
1
Note
1
DC coils require an early break NC auxiliary contact C320KGD1 (1NCI) or C320KGD2 (1NO-1NCI). Order separately, not included with replacement coil.
DC Coil
Voltage
Inrush (Maximum) Sealed (Maximum)
Coil
SuffixAmperes Watts Amperes Watts Class Part Number
15, 25, 30 and 40A—Two- and Three-Pole (Series D1)
12 5.8 69 0.272 3.27 1R Class F, 155°C 9-3254-2
24 2.9 69 0.13 3.12 1T 9-3254-3
48 1.5 72 0.07 3.37 1W 9-3254-4
120 0.61 73 0.03 3.68 1A 9-3254-5
50A—Two- and Three-Pole (Series D1)
12 5.8 69 0.272 3.27 1R Class F, 155°C 9-3255-2
24 2.9 69 0.13 3.12 1T 9-3255-3
48 1.5 72 0.07 3.37 1W 9-3255-4
120 0.61 73 0.03 3.68 1A 9-3255-5
15, 25, 30 and 40A—Two- and Three-Pole (Series C1)
12 4.7 51 232 mA 1.8 1R Class F, 155°C 9-3126-1
24 2.7 64 110 mA 2.4 1T 9-3126-2
48 1.4 65 55 mA 2.5 1W 9-3126-3
60 and 75A—Two- and Three-Pole; 25, 30 and 40A—Four-Pole (Series C1)
12 15.4 126 0.434 5.26 1R Class F, 155°C 9-3257-1
24 6.2 88.4 0.211 5.12 1T 9-3257-2
48 2.9 76.2 0.102 4.92 1W 9-3257-3
120 1.1 67.3 0.044 5.32 1A 9-3257-4
A1 (Top)
NCI
Conductor Extending
from Bottom of Coil
Early Break Normally
Closed Auxiliary Contact
Hold (Seal) Pick-Up
A2 (Top)