4.2
Definite Purpose Contactors and Starters
Contactors
Options
When Ordering Specify
To order replace letter in the 6th position of catalog number
with letter F. Example: C25BNF240A.
Compact Factory Installed Options
Technical Data and Specifications
20–40A, Compact Single- and Two-Pole—C25
Coil Characteristics
Description
Box lugs with quick connects for 20–40A contactors
Single-pole
Single-pole with shunt
Two-pole
Description Specification
Insulation voltage 690V
Current rated and hp/kw rated contacts Double break
Magnet coil Class F, 155°C
Contact arc covers Standard on all contactors
Standard power terminals 5/16 in hex washer head screws
Quad (4) quick connect terminals on all line and load terminals
Box lugs available as option
Line and load terminal designations Marked on contactors
Operating temperature range –13° to 158°F (–25° to 70°C)
Terminal wire range
Hex washer head screws 6–10 AWG, 30 lb-in torque rating
Box lugs 6–10 AWG, 35 lb-in torque rating
8 AWG, 40 lb-in torque rating
6–4 AWG, 45 lb-in torque rating
Mounting position Vertical, horizontal or tabletop
AC Coil
Voltage 50/60 Hz
Maximum
Inrush VA
Maximum
Sealed VA
Maximum
Sealed Watts
Single-Pole
24 33 6 2
120 33 6 2
208/240 33 6 2
277 33 6 2
Tw o - P o l e
24 41 6.5 3
120 41 6.5 3
208/240 41 6.5 3
277 41 6.5 3
480 41 6.5 3