4.3
Definite Purpose Contactors and Starters
Starters
Electronic Overload Relays up to 1500A, continued
Wiring Diagrams
Single-Phase Connections Three-Phase Connections
Specification
Description 45 mm 55 mm
Electrical/EMC
Radiated emissions
IEC 60947-4-1-Table 15
EN 55011 (CISPIR 11) Group 1, Class A, ISM
30 MHz to 1000 MHz 30 MHz to 1000 MHz
Conducted emissions
IEC 60947-4-1-Table 14
EN 55011 (CISPIR 11) Group 1; Class ISM
0.15 MHz to 30 MHz 0.15 MHz to 30 MHz
ESD immunity
IEC 60947-4-1 (Table 13)
±8 kV air, ±6 kV contact ±8 kV air, ±6 kV contact
Radiated immunity
IEC 60947-4-1
IEC 61000-4-3
10V/m 80 MHz–1000 MHz
3V/m from 1.4 to 2.7 GHz
80% amplitude modulated
1 kHz sine wave
10V/m 80 MHz–1000 MHz
3V/m from 1.4 to 2.7 GHz
80% amplitude modulated
1 kHz sine wave
Conducted immunity
IEC 60947-4-1, IEC 61000-4-6
140 dub (10V rms)
150 kHz–100 MHz
140 dub (10V rms)
150 kHz–100 MHz
Fast transient immunity
IEC 60947-4-1 (Table 13)
IEC 61000-4-4
±4 kV using direct method
with accessory installed in expansion bay
±2 kV using direct method
±4 kV using direct method
with accessory installed in expansion bay
±2 kV using direct method
Surge immunity
IEC 60947-4-1 (Table 13)
IEC 61000-4-5 a Class 4
Three-phase power inputs:
±4 kV line-to-line (DM)
±4 kV line-to-ground (CM)
Three-phase power inputs:
±4 kV line-to-line (DM)
±4 kV line-to-ground (CM)
With accessory installed in expansion bay:
±2 kV line-to-line (DM) –>1.2/50 us;
2 kV line-to-earth, 1 kV line-to-line
±4 kV line-to-ground (CM)
With accessory installed in expansion bay:
±2 kV line-to-line (DM) –>1.2/50 us;
2 kV line-to-earth, 1 kV line-to-line
±4 kV line-to-ground (CM)
Power freq. magnetic field immunity
IEC 60947-4-1, IEC 61000-4-8
30A/m, 50 Hz 30A/m, 50 Hz
Electromagnetic field
IEC 60947-4-1 Table 13, IEC 61000-4-3
10 V/m 10 V/m
Distortion IEEE 519 5% THD max., 5th harmonic 3% max. 5% THD max., 5th harmonic 3% max.
Electrostatic discharge (ESD)
IEC 61000-4-2, EN 61131-2
4 kV contact
8 kV air discharge
4 kV contact
8 kV air discharge
Electrical fast transient (EFT)
IEC 61000-4-4, EN 61131-2
±2 kV using direct method ±2 kV using direct method
Surge immunity
IEC 61000-4-5, EN 61131-2
±2 kV line-to-ground (CM) ±2 kV line-to-ground (CM)
1NO Aux. Contact
(When Supplied)
Reset
Wire “D”
(Supplied with
1NO Aux. Contact)
Wire “C”
(Supplied with Common Control)
1
13
14
L1 L2
T1
4/T22/T1
T2
AC Motor
98
97
96
95
AC Motor
T2
L1 L2 L3
1
13
14
T1
6/T32/T1 4/T2
T3
98
97
96
95
Wire “D”
(Supplied with
1NO Aux. Contact)
Wire “C”
(Supplied with Common Control)
1NO Aux. Contact
(When Supplied)