Product Brochure
V5-T4-34 Volume 5—Motor Control and Protection CA08100006E—May 2013 www.eaton.com
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4.3
Definite Purpose Contactors and Starters
Starters
Overload Relays
These tripping characteristics are the mean values of the spread at 20°C ambient temperature
in a cold state.
Tripping time depends on response current. With devices at operating temperature, the
tripping time of the overload relay reduces to approximately 25% of the read off value.
Specific characteristics for each individual setting range can be found in MN03402001E.
Overload Relays
Notes
1
Ambient temperature operating range to IEC/EN 60947, PTB: –5° to 50°C [23° to 122°F].
2
6 mm
2
flexible with ferrules to DIN 46228.
3
Main contact terminal capacity, solid and stranded conductors with ferrules: When using two conductors use identical cross-section.
Description
XTOB … CC1
Specification
XTOB … DC1
Specification
General
Climatic proofing Damp heat, constant, to IEC 60068-2-78;
Damp heat, cyclic, to IEC 60 068-2-30
Damp heat, constant, to IEC 60068-2-78;
Damp heat, cyclic, to IEC 60 068-2-30
Ambient temperature range
1
–25° to 50°C [–13° to 122°F] –25° to 50°C [–13° to 122°F]
Temperature compensation Continuous Continuous
Mechanical shock resistance (IEC/EN 60068-2-27)
Half-sinusoidal shock 10 ms 10g 10g
Degree of protection IP20 IP20
Protection against direct contact when actuated
from front (IEC 536)
Finger and back of hand proof Finger and back of hand proof
Insulation voltage (U
i
) Vac 690 690
Overvoltage category/pollution degree III/3 III/3
Impulse withstand voltage (U
imp
) Vac 6000 6000
Operational voltage (U
e
) Vac 690 690
Safe isolation to VDE 0106 Part 101 and Part 101/A1
Between auxiliary contacts and main contacts (Vac) 440 440
Between main contacts (Vac) 440 440
Overload relay setting range 0.1–32A 6–75A
Temperature compensation residual error >20°C (%/K)
<
0.25
<
0.25
Current heat loss (3 conductors)
Lower value of setting range, W 2.5 3
Upper value of setting range, W 6 7.5
Terminal capacity 2 x (1–6) 2 x (1–6)
Solid, mm
2
2 x (1–4) 1 x 25
Flexible with ferrule, mm
2
2 x (1–6)
2
2 x (1–10)
3
Solid or stranded, AWG 14-8 14-2
Terminal screw M4 M6
Tightening torque Nm (lb-in) 1.8 (16) 3.5 (31)
Tools
Pozidrive screwdriver Size 2 Size 2