Product Brochure
Volume 5—Motor Control and Protection CA08100006E—May 2013 www.eaton.com V5-T4-33
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4
4.3
Definite Purpose Contactors and Starters
Starters
Renewal Parts
Overload Relays
Technical Data and Specifications
Terminal Wire Sizes
Note
1
Line side (contactor) torque ratings can be found on Page V5-T4-14.
Power Terminals—Load—Cu Only (Stranded or Solid)
Motor Full
Load Amperes Suffix Code
For use with
Contactor
Ampere Range
Overload Relay
Catalog Number
Frame C
0.1–0.16 P16 15–25A XTOBP16CC1DP
0.16–0.24 P24 15–25A XTOBP24CC1DP
0.24–0.4 P40 15–25A XTOBP40CC1DP
0.4–0.6 P60 15–25A XTOBP60CC1DP
0.6–1 001 15–25A XTOB001CC1DP
1–1.6 1P6 15–25A XTOB1P6CC1DP
1.6–2.4 2P4 15–25A XTOB2P4CC1DP
2.4–4 004 15–25A XTOB004CC1DP
4–6 006 15–25A XTOB006CC1DP
6–10 010 15–25A XTOB010CC1DP
10–16 016 15–25A XTOB016CC1DP
16–24 024 15–25A XTOB024CC1DP
24–32 032 15–25A XTOB032CC1DP
Frame D
6–10 010 30–45A XTOB010DC1DP
10–16 016 30–45A XTOB016DC1DP
16–24 024 30–45A XTOB024DC1DP
24–40 040 30–45A XTOB040DC1DP
40–57 057 30–45A XTOB057DC1DP
Line Side (Contactor)
1
Wire Range—Solid or Stranded
Terminal Type Power Terminals Coil Terminals
Screw/pressure plate 8–14 AWG 12–16 AWG
Box lug: 15–45A 4–14 AWG 12–16 AWG
Terminal Range Torque Rating
15 and 25A 14–8 AWG 16 lb-in (14–8 AWG)
30, 40 and 45A 14–2 AWG 31 lb-in (14–2 AWG)
Control Terminals—Cu Only
12–16 AWG stranded, 12–14 AWG solid