Definite Purpose Contactors and Starters
Starters
Standard Trip—Class 20 Heater Packs
Manual or Automatic Reset
Heater packs are shipped three to a carton.
Catalog numbers listed below are for three heater packs.
Standard Trip Ratings
Technical Data and Specifications
Terminal Wire Sizes
Power Terminals—Load—Cu Only (Stranded or Solid)
Notes
1
For motor full load amperes between listed values, adjust dial clockwise for higher or counter-
clockwise for lower motor currents. The currents listed are for 1.5 service factor motors.
A position adjustment is provided for 1.0 service factor motors.
2
Set of three heater packs are required for both single- and three-phase applications.
3
Line side (contactor) torque ratings can be found on Page V5-T4-14.
Motor Full Load Ampere Rating
1
Catalog Number
2
(Includes Three Heater
Packs)
Dial Position
ABCD
0.254 0.306 0.359 0.411 H2001B-3
0.375 0.452 0.53 0.607 H2002B-3
0.56 0.676 0.791 0.907 H2003B-3
0.814 0.983 1.15 1.32 H2004B-3
1.2 1.45 1.71 1.96 H2005B-3
1.79 2.16 2.53 2.9 H2006B-3
2.15 2.6 3.04 3.49 H2007B-3
3.23 3.9 4.56 5.23 H2008B-3
4.55 5.5 6.45 7.4 H2009B-3
6.75 8.17 9.58 11 H2010B-3
9.14 10.8 12.4 14 H2011B-3
14 16.9 19.9 22.8 H2012B-3
18.7 22.7 26.7 30.7 H2013B-3
23.5 28.5 33.5 38.5 H2014B-3
29 34 39.1 44.1 H2015B-3
39.6 45.5 51.5 57.4 H2016B-3
53.9 60.9 67.9 74.9 H2017B-3
Trip Curves, see Page V5-T4-28.
Line Side (Contactor)
3
Wire Range—Solid or Stranded
Terminal Type Power Terminals Coil Terminals
Screw/pressure plate 8–14 AWG 12–16 AWG
Box lug: 25–50A 4–14 AWG 12–16 AWG
Box lug: 60A 3–14 AWG 12–16 AWG
Terminal Range Torque Rating
25 and 30A 14–6 AWG 20 lb-in (14–10 AWG)
40, 50 and 60A 14–2 AWG 35 lb-in (14–10 AWG)
40 lb-in (8 AWG)
45 lb-in (6–4 AWG)
50 lb-in (3–2 AWG)
Control Terminals—Cu Only
12–16 AWG stranded, 12–14 AWG solid