4.3
Definite Purpose Contactors and Starters
Starters
Accessories
Contactor Accessories, see Pages V5-T4-11 and V5-T4-12.
Locking Cover for Overload Relay
Snap-on transparent or opaque plastic panel for covering access port to the overload relay trip
setting dial—helps prevent accidental or unauthorized changes to trip and reset setting.
Locking Cover for Overload Relay
Separate Enclosures
Separate Enclosures—NEMA 1
Heater Packs
Fast Trip—Class 10 Heater Packs
Manual or Automatic Reset
Heater packs are shipped three to a carton.
Catalog numbers listed below are for three heater packs.
Fast Trip Ratings
Notes
1
For motor full load amperes between listed values, adjust dial clockwise for higher or counter-
clockwise for lower motor currents. The currents listed are for 1.5 service factor motors.
A position adjustment is provided for 1.0 service factor motors.
2
Set of three heater packs are required for both single- and three-phase applications.
Description
Minimum Order
Quantity
(Std. Pkg.) Catalog Number
Clear cover, no accessibility 50 C320PC3
Gray cover, no accessibility, with auto only nib 50 C320PC4
Gray cover, no accessibility, with manual only nib 50 C320PC5
Gray cover with FLA dial accessibility, A, B, C, D positions
and auto only nib
50 C320PC6
Gray cover with FLA dial accessibility, A, B, C, D positions
and manual only nib
50 C320PC7
Application Catalog Number
25 and 30A C799B11
40, 50 and 60A C799B13
Motor Full Load Ampere Rating
1
Catalog Number
2
(Includes Three Heater
Packs)
Dial Position
ABCD
0.26 0.313 0.367 0.42 H2101B-3
0.384 0.464 0.543 0.623 H2102B-3
0.57 0.688 0.806 0.924 H2103B-3
0.846 1.02 1.2 1.37 H2104B-3
1.28 1.55 1.83 2.1 H2105B-3
1.92 2.33 2.74 3.15 H2106B-3
2.3 2.79 3.28 3.77 H2107B-3
3.38 4.1 4.82 5.54 H2108B-3
4.96 6.03 7.09 8.16 H2109B-3
7.07 8.58 10.1 11.6 H2110B-3
9.6 11.2 12.8 14.4 H2111B-3
14.4 17.5 20.7 23.8 H2112B-3
18.7 21.8 25 28.1 H2113B-3
23.5 27.3 31 34.8 H2114B-3
28.3 32.6 37 41.3 H2115B-3
36.6 42.3 48.1 53.8 H2116B-3
53.8 60.8 67.9 74.9 H2117B-3
Trip Curves, see Page V5-T4-28.