4.2
Definite Purpose Contactors and Starters
Contactors
For Global Line Only
DC Ratings (Global Listed Line Only)
Lighting Duty Ratings (Global Listed Line Only)
IEC/CE Ratings (IEC 60947-4-1, EN 60947-4-1) for 15A through 50A
C25 D–Contactors (Global Listed Line Only)
Two-Pole, 15–30A Inductive Two-Pole, 40A Inductive Three-Pole, 15–30A Inductive Three-Pole, 40A Inductive
UL/CSA DC-3/DC-5 UL/CSA DC-3/DC-5 UL/CSA DC-3/DC-5 UL/CSA DC-3/DC-5
Voltage FLA hp I
e
FLA hp I
e
FLA hp I
e
FLA hp I
e
240 Vdc three poles in series — — — — — — 4 3/4 4 5 1 5
120 Vdc three poles in series — — — — — — 8 3/4 8 10 1 10
120 Vdc two poles in series 5.5 1/2 5.5 8 3/4 8 5.5 1/2 5.5 8 3/4 8
120 Vdc per pole 2 1/10 2 3.5 1/4 3.5 2 1/10 2 3.5 1/4 3.5
24 Vdc per pole 15 — 15 20 — 20 15 — 15 20 — 20
C25D_ Inductive Rating Tungsten and Ballast (480V)
25A 30A
30A 40A
40A 50A
50A 60A
C25D_ AC-1 (I
c
)AC-3 (I
e
)AC-4 (I
e
)AC-8a
Inductive Rating 480V 600V 480V 600V 480V 600V 480V 600V
15A 20A 20A 15A 15A 15A — 15A 15A
25A 30A 30A 25A 25A 25A — 25A 25A
30A 40A 40A 30A 30A 30A — 30A 30A
40A 50A — 40A — 40A — 40A —
50A 65A 65A 50A 50A 50A — 50A 50A