Datasheet

04/19/2017 186260 - HPL-ED2017 V31.0 EN 2 / 3
Technical�data
General
Standards IEC/EN 60947-5-1
VDE 0660
Certifications CE, UL, CSA
Operating frequency Operations/h
100
Operating torque Nm
0.5
Tightening torque Threaded ring Nm 2
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Degree of Protection IP66 (front)
IP65 (on rear)
Mounting position As required
Mechanical shock resistance, shock duration 11 ms g > 30
Contacts
Rated impulse withstand voltage U
imp
V AC 4000
Rated insulation voltage U
i
V 250
Overvoltage category/pollution degree III/3
Control circuit reliability
At 17 V DC/7 mA H
F
N/O contact: statistically determined 1 failure per 17 × 106 operations
N/C contact: statistically determined 1 failure per 0.9 × 10
6
Operations
Max. short-circuit protective device
Fuse gG/gL A 4
Rated conditional short-circuit current Iq kA 1
Switching�capacity
Rated operational current I
e
A
AC-15
24 V I
e
A 4
DC-13
24 V I
e
A 3
Cable characteristics
Design Cable end open
Cable Length m 1
Material characteristic PUR
Diameter mm 4.7
Design�verification�as�per�IEC/EN�61439
Technical data for design verification
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 70
Technical�data�ETIM�6.0
Low-voltage industrial components (EG000017) / Selector switch, complete (EC001029)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Command and alarm device / Selector switch, complete unit (ecl@ss8.1-27-37-12-43
[ACN984008])
Number of switch positions 2
Type of control element Key
Suitable for illumination No
With lamp No
Colour button Black
Hole diameter mm 22
Width opening mm 0
Height meter opening mm 0
Switching function latching Yes
Spring-return No