Specifications

96 Distribution Products Catalog CA08101001E—October 2010 www.eaton.com
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16.6
Tr a n s f er Switches
Standard and Optional Features
Magnum-Based—Automatic Transfer Switch Features
S = Standard, O = Optional
Open Transition Closed Transition
ATVIMG NTVEMG BIVIMG CTVIMG CBVIMG CTVCMG CBVCMG
Feature
Number Description
Magnum
Fixed and
Drawout
Mount
ATC-600
Controller
Magnum
Fixed and
Drawout
Mount
Non-Automatic
Transfer
Bypass
Isolation
Magnum
Drawout
ATC-600
Controller
Magnum
Fixed and
Drawout
Mount
ATC-800
Closed Transition
Magnum
Fixed and
Drawout
Mount
ATC-800
Closed Transition
Magnum
Soft Load
Drawout
ATC-5000
Soft Load
Bypass
Isolation
Soft Load
Magnum
Drawout
ATC-5000
Soft Load
1
1a
Timers
Time delay normal to emergency (TDNE)
Fixed 2 seconds or 15 seconds
——
Adjustable 0–1800 seconds S S S S S S
2Time delay engine start (TDES)
Fixed 3 seconds
——
Adjustable 0–120 seconds S S S S S S
3Time delay emergency to normal (TDEN)
Fixed 1 minute
——
Adjustable 0–1800 seconds S S S S S S
4Time delay engine cooldown (TDEC)
Fixed 5 minutes
——
Adjustable 0–1800 seconds S S S S S S
5
5H
Emergency (S2) source sensing
Phase reversal 0 0 0 0 0 0
5J All-phase undervoltage/underfrequency S S S S S S
5K All-phase overvoltage/overfrequency S S S S S S
5L All-phase voltage unbalance and phase loss
5N All-phase overfrequency
6
6B
System or engine test
System test pushbutton S S S S S S
6D Maintained two-position test switch O 0 0 0 0 0
6H Maintained four-position test switch 0 S 0 0 0 S
7Time delay emergency fail (TDEF)
Fixed 6 seconds
——
7a Time delay emergency fail (TDEF)
Adjustable 0–6 seconds)
S—SS S SS
8
8C
Pushbutton bypass
Bypass TDEN S S S S S S
8D Bypass TDNE S S S S S S
9
9B
Maintenance selector switch
Electrical operator isolator switch 0 0 0 0 0 0
10
10B
Preferred source selector
Utility to utility or utility to generator S S S S S S
10D Generator to generator S S S S S S
12C
Indicating lights
Normal (S1) source connected S S S S S S S
12D Emergency (S2) source connected S S S S S S S
12G Normal (S1) source available S S S S S S S
12H Emergency (S2) source available S S S S S S S
12L Normal (S1) source tripped (requires Feature 16) 0 0 0 0 0 0 0
12M Emergency (S2) source tripped (requires Feature 16) 0 0 0 0 0 0 0