Specifications
Distribution Products Catalog CA08101001E—October 2010 www.eaton.com 93
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16.6
Tr a n s f er Switches
Standard and Optional Features
Breaker-Based—Automatic Transfer Switch Features, continued
Notes
Select 16S for service entrance rating on RLC1.
Ground fault protection is required for service disconnects rated 1000A or more if the electrical service is
a solidly grounded wye system of more than 150V to ground but not exceeding 600V phase to phase.
S = Standard, O = Optional
Open Transition
Closed
Transition
ATV1
ATH1
ATV3
ATH3
ATVI
ATH
NTHE
NTVE
MTHX
MTVX BIHI MBHE
Feature
Number Description
Light
Commercial
Molded
Case Switch
ATC-100
Controller
Molded
Case Switch
ATC-300
Controller
Molded
Case Device
ATC-600
Controller
Molded
Case Switch
Non-Automatic
Transfer
Switch
Molded
Case Switch
Manual
Transfer Switch
Molded
Case Switch
Bypass
Isolation
Switch
ATC-600
Molded
Case Switch
Maintenance
Bypass
26
26D
Normal (S1) source sensing
Go to emergency (S2) input — S S — — S —
26H Phase reversal protection — S 0 — — 0 —
26J All-phase undervoltage/underfrequency — S S — — S —
26K All-phase overvoltage/overfrequency — S S — — S —
26L Three-phase voltage unbalance/phase loss — S — — — — —
26M Allows operation with generator with utility sensing
(option available only through a field-installed kit)
0——— — ——
26P All-phase undervoltage S — — — — — —
29
29G
Alternative transfer modes of operation
Selector switch for automatic or non-automatic
operation (switch must be labeled as non-automatic)
—0 0 — — ——
29J Automatic transfer operation with selectable
(via programming) automatic or non-automatic
retransfer operation with fail-safe
——0 — — 0 —
32
32A
Delayed transfer operation modes
Time delay neutral adjustable 0–120 seconds
(available on three-position contactors and
breaker-based design)
—S S— — ——
32B Load voltage decay adjustable — — 0 — — — —
32C 2–30% nominal voltage
In-phase monitor defaults to load voltage decay
———— — ——
32D In-phase monitor defaults to time delay neutral — — — — — — —
32E Delay transition timer adjustable 3–60 seconds — — — S — — —
32F In-phase monitor (2-position contactors only) — — — — — — —
32G Time delay neutral fixed 0 or 2 seconds (available
on 3-position contactors and breaker-based design)
S——— — ——
34
34A
Logic extender cable
48 inches (1219 mm) — — 0 0 — 0 —
34C 96 inches (2438 mm) — — 0 0 — 0 —
34E 144 inches (3658 mm) — — 0 0 — 0 —
35A Pretransfer Sig-l contacts 1 Form C — S 0 — — 0 —
36 Load shed from emergency — — S — — S —
37 Go to isolated position (not SE rated)
Rated as suitable for use as service equipment
(requires 16B or 16N or 16E or 16S)
000— — ——
37A Without ground fault protection
—0 0 0 — 0 —
37B With ground fault protection — 0 0 0 — 0 —
38
38A
Stainless steel device covers
SS cover for device plate or service
equipment disconnect
—0 0 0 — 0 —
38B SS cover for controller 0 0 0 0 — 0 —