Specifications

Distribution Products Catalog CA08101001E—October 2010 www.eaton.com 91
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16.6
Tr a n s f er Switches
Standard and Optional Features
Breaker-Based—Automatic Transfer Switch Features
S = Standard, O = Optional
Open Transition
Closed
Transition
ATV1
ATH1
ATV3
ATH3
ATVI
ATH
NTHE
NTVE
MTHX
MTVX BIHI MBHE
Feature
Number Description
Light
Commercial
Molded
Case Switch
ATC-100
Controller
Molded
Case Switch
ATC-300
Controller
Molded
Case Device
ATC-600
Controller
Molded
Case Switch
Non-Automatic
Transfer
Switch
Molded
Case Switch
Manual
Transfer Switch
Molded
Case Switch
Bypass
Isolation
Switch
ATC-600
Molded
Case Switch
Maintenance
Bypass
1
1a
Timers
Time delay normal to emergency (TDNE)
Fixed 2 seconds or 15 seconds
S—
Adjustable 0–1800 seconds S S S
2Time delay engine start (TDES)
Fixed 3 seconds
S—
Adjustable 0–120 seconds S S S
3Time delay emergency to normal (TDEN)
Fixed 1 minute
S—
Adjustable 0–1800 seconds S S S
4Time delay engine cooldown (TDEC)
Fixed 5 minutes
S—
Adjustable 0–1800 seconds S S S
5
5H
Emergency (S2) source sensing
Phase reversal S O O
5J All-phase undervoltage/underfrequency S S S S
5K All-phase overvoltage/overfrequency S S S
5L All-phase voltage unbalance and phase loss S
5N All-phase overfrequency S
6
6B
System or engine test
System test pushbutton S S S S
6D Maintained two-position test switch O O
6H Maintained four-position test switch O O
7Time delay emergency fail (TDEF)
Fixed 6 seconds
S—
7a Time delay emergency fail (TDEF)
Adjustable 0–6 seconds)
—S S S
8
8C
Pushbutton bypass
Bypass TDEN
—S S S
8D Bypass TDNE S S S
9
9B
Maintenance selector switch
Electrical operator isolator switch O O O
——O— O—
10
10B
Preferred source selector
Utility to utility or utility to generator
10D Generator to generator O O
12C
Indicating lights
Normal (S1) source connected S S S S S
12D Emergency (S2) source connected S S S S S
12G Normal (S1) source available S S S S S
12H Emergency (S2) source available S S S S S
12L Normal (S1) source tripped (requires Feature 16) O O O O
12M Emergency (S2) source tripped (requires Feature 16) O O O O