Tr a n s f er Switches
Standard and Optional Features
Contactor-Based—Automatic Transfer Switch Features, continued
S = Standard, O = Optional
Open Transition
Closed
Transition
RLC1 ATC1 ATC3 ATC8 BIC3 BIC8 CBC8
Feature
Number Description
Residential
Contactor
Switch
ATC-100
Controller
Contactor
Switch
ATC-100
Controller
40–600A Only
Contactor
Switch
ATC-300
Controller
40–1200A
Contactor
Switch
ATC-800
Controller
Open
Transition
Bypass
Isolation
Contactor
Switch Open
Transition
ATC-300
Controller
Bypass
Isolation
Contactor
Switch
ATC-800
Controller
Bypass
Isolation
Contactor
Switch Closed
Transition
ATC-800
Controller
18 Metering OOOOOO
IQ 130 OOOOOO
IQ 140 OOOOOO
IQ 150 OOOOOO
IQ 250 OOOOOO
IQ 260 OOOOOO
PXM 2250 OOOOOO
PXM 2260 OOOOOO
PXM 2270 OOOOOO
18W Analog ammeter one per phase OOOOOO
21A Non-standard terminals ———————
23
23A
Plant exerciser
Selectable—disabled/7-, 14-, 28-day interval,
FIXED 15 minutes, load/no load, with fail-safe
SS—————
23J Selectable—disabled/7 day interval,
0–600 minutes, load/no load, with fail-safe
———S —S S
23K Selectable—disabled/7-, 14-, 28-day interval,
0–600 minutes, load/no load, with fail-safe
——S —S ——
23L 24-hour, 7-day, 365-day programmable
programmable plant exciser
——OOOOO
26
26D
Normal (S1) source sensing
Go to emergency (S2) input S S S S S
26H Phase reversal protection S O 0 0 O
26J All-phase undervoltage/underfrequency S S S S S
26K All-phase overvoltage/overfrequency S S S S S
26L Three-phase voltage unbalance/phase loss S ————
26M Allows operation with generator with utility sensing
(option available only through a field-installed kit)
OO—————
26P All-phase undervoltage S S —————
29
29G
Alternative transfer modes of operation
Selector switch for automatic or non-automatic
operation (switch must be labeled as non-automatic)
——OOOOO
29J Automatic transfer operation with selectable
(via programming) automatic or non-automatic
retransfer operation with fail-safe
———OOOO