Specifications

Distribution Products Catalog CA08101001E—October 2010 www.eaton.com 75
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16.5
Tr a n s f er Switches
ATC Controllers
Standards and Certifications
UL listed component
IEC 61000-4-2, 61000-4-3,
61000-4-4, 61000-4-5,
61000-4-6, 61000-4-11
CISPR 11, Class B
FCC Part 15, Class B
Technical Data and Specifications
ATC-100 Controller Specifications
Adjustable Features with Range and Factory Default
Description Specification
Input control voltage 95 to 145 Vac 50/60 Hz
Voltage measurements of Utility V
AB
Generator V
AB
Utility V
BC
Generator V
BC
Utility V
CA
Generator V
CA
Voltage measurement range 0 to 575 Vac rms (50/60 Hz)
Voltage measurement accuracy ±1% of full scale
Frequency measurements of Generator
Frequency measurement range 40 Hz to 70 Hz
Frequency measurement accuracy ±0.3 Hz over the measurement range
Operating temperature range –20 to +70°C (–4 to +158°F)
Storage temperature range –0 to +85°C (–22 to +185°F)
Operating humidity 0 to 95% relative humidity (noncondensing)
Operating environment Resistant to ammonia, methane, nitrogen, hydrogen and hydrocarbons
Generator start relay 5A, 1/6 hp @ 250 Vac
5A at 30 Vdc with a 150W maximum load
K1, K2 relays 10A, 1–3 hp @ 250 Vac
10A @ 30 Vdc
Enclosure compatibility NEMA 1, NEMA 3R and NEMA 12
UV-resistant ATC-100 faceplate
Setpoint
Fixed/
Adjustable Description Range
Factory Default
Breakers Contactors
TDES Fixed Time delay engine start 3 seconds 3 seconds 3 seconds
TDNE Jumper-selectable Time delay normal to emergency 2 or 15 seconds 15 seconds 15 seconds
TDEN Fixed Time delay emergency to normal 5 minutes 5 minutes 5 minutes
TDEC Fixed Time delay engine cool-off 1 minute 1 minute 1 minute
NOM FREQ Jumper-selectable Nominal frequency 50 or 60 Hz As ordered As ordered
NOM VOLTS Jumper-selectable Nominal voltage 120, 208, 220, 230, 240, 380, and 480V As ordered As ordered
S1 UV DROP Fixed Utility undervoltage dropout 80% of NOMV 80% of NOMV in volts 80% of NOMV in volts
S2 UV DROP Fixed Generator undervoltage dropout 80% of NOMV 80% of NOMV in volts 80% of NOMV in volts
S1 UV PICK Fixed Utility undervoltage pickup 90% of NOMV 90% of NOMV in volts 90% of NOMV in volts
S2 UV PICK Fixed Generator undervoltage pickup 90% of NOMV 90% of NOMV in volts 90% of NOMV in volts
S2 UF DROP Fixed Utility underfrequency dropout 90% of NOMF 90% of NOMF in hertz 90% of NOMF in hertz
S2 UF PICK Fixed Generator underfrequency pickup 95% of NOMF 95% of NOMF in hertz 95% of NOMF in hertz
S2 OF DROP Jumper-selectable Generator overfrequency dropout Off or 115% of NOMF (contactor) Off 115%
S2 OF PICK Jumper-selectable Generator overfrequency pickup Off or 110% of NOMF Off 110%
Generator test Jumper-selectable Generator test programming 7-, 14- or 28-day 7-day 7-day
Test mode Jumper-selectable Test mode Off, No Load, Load Off Off
TER Fixed Engine run test time 15 minutes 15 minutes 15 minutes
PHASES Jumper-selectable Three-phase or single-phase 1 or 3 As ordered As ordered
TDEF Fixed Time delay emergency fail timer 6 seconds 6 seconds 6 seconds
TDN Jumper-selectable Time delay neutral Disabled (0 seconds) or enabled (2 seconds) Enabled (2 seconds) Enabled (2 seconds)