Specifications

74 Distribution Products Catalog CA08101001E—October 2010 www.eaton.com
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16.5
Tr a n s f er Switches
ATC Controllers
ATC-100 Controller
Contents
Description Page
Product Selection Guide. . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
ATC-100 Controller
Standards and Certifications . . . . . . . . . . . . . . . . . . . . . . 75
Technical Data and Specifications . . . . . . . . . . . . . . . . . . 75
ATC-300 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
ATC-600 Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
ATC-800 Transition Controller. . . . . . . . . . . . . . . . . . . . . . . . 81
ATC-100 Controller
Product Description
The ATC-100 Controller is a
comprehensive, multifunction,
microprocessor-based ATS
controller. It is a compact,
self-contained, panel-
mounted device designed to
replace traditional relay and
solid-state logic panels.
Application Description
The ATC-100 Controller
provides both fixed and
jumper-selectable settings
to allow for a range of
applications. It operates from
all system voltages between
120 and 480 Vac, single-
phase and three-phase, at 50
or 60 Hz. In addition, a period
of no control power operation
is provided. The ATC-100
Controller monitors the
condition of the three-phase
line-to-line voltage and
frequency of both the
utility and generator power
sources. It can also be set
up for single-phase operation.
The ATC-100 controller
provides the necessary
intelligence to ensure that
the transfer switch operates
properly through a series of
sensing and timing functions.
The ATC-100 controller
can be used with both the
breaker-based design and
the contactor-based design.
See Page 75 for ranges and
factory settings.
Features, Benefits and Functions
Standard Features
Auxiliary relay contacts:
Source 1 present
2NO and 2NC
Source 2 present
2NO and 2NC
Switch position indication
contacts:
Source 1 position
1NO and 1NC
Source 2 position
1NO and 1NC
Source 1 and Source 2
sensing:
Undervoltage/under
frequency
Overvoltage/over
frequency
Controller settings via
jumpers located at the
rear of the unit
Mimic diagram with source
available and connected
LED indication
Time-stamped history log
System TEST pushbutton
Selectable—OFF, daily,
7-, 14-, 28-day interval
fixed run time 15 minutes
no load/load with fail-safe
Monitor utility and
generator power source
voltages and generator
power source frequency
Provide undervoltage
protection of the utility and
generator power sources
Provide underfrequency
and overfrequency
protection of the utility and
generator power source
Permit easy customer
setup
Permit system testing
Provide faceplate source