Specifications

72 Distribution Products Catalog CA08101001E—October 2010 www.eaton.com
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16.5
Tr a n s f er Switches
ATC Controllers
ATC Controller Specification Selection Chart
Note
Features are order specific. Not all features are supplied as standard.
Specification Description
ATC-100 ATC-300 ATC-600 ATC-800
Programming Selections
Time delay normal to emergency 3 seconds (fixed) 0–1800 seconds 0–1800 seconds 0–1800 seconds
Time delay emergency to normal 5 minutes (fixed) 0–1800 seconds 0–1800 seconds 0–1800 seconds
Time delay engine cooldown 5 minutes (fixed) 0–1800 seconds 0–1800 seconds 0–1800 seconds
Time delay engine start 3 seconds (fixed) 0–120 seconds 0–120 seconds 0–120 seconds
Time delay neutral N/A 0–120 seconds 0–120 seconds or based on
load voltage decay of 2%–30%
of nominal
0–120 seconds or based on
load voltage decay of 2%30%
of nominal
Time delay Source 2 fail N/A 0–6 seconds 0–6 seconds 0–6 seconds
Time delay voltage unbalance N/A 10–30 seconds N/A N/A
Voltage unbalance three-phase N/A 0 or 1 (1 = enabled)
% of unbalanced voltage dropout N/A 5% to 20% (DO) dropout
–2% to 3% (PU)
N/A N/A
Phase reversal three-phase N/A OFF, ABC, CBA N/A N/A
In-phase N/A 0 or 1 (1 = enabled) Enabled or disabled Enabled or disabled
Load sequencing N/A N/A Up to 10 devices
(via sub-network)
Up to 10 devices
(via sub-network)
Pretransfer signal N/A 1–120 seconds
(Form C contact)
0–120 seconds
(up to 10 devices via sub-network)
0–120 seconds
(up to 10 devices via sub-network)
Plant exerciser Selectable day, off, 7-, 14-,
28-day interval, 15 minutes
run time, no load
Programmable—off, daily or
7-, 14-, 28-day intervals,
0–600 minutes, load or no load
Programmable—disabled or
7-day interval, 0–600 minutes,
load or no load
Programmable—disabled or 7- day
interval, 0–600 minutes, load or
no load
Preferred source selection N/A N/A Source 1 or 2 or none Source 1 or 2 or none
Commitment to transfer in TDNE N/A N/A Enabled or disabled Enabled or disabled
Retransfer mode N/A N/A Automatic or manual Automatic or manual
Auto daylight savings time adjustment N/A 0 or 1 (1 = enabled)
System selection Utility/generator Utility/generator or dual utility Utility/generator or dual utility
or dual generator
Utility/generator or dual utility
or dual generator
Additional information PA01600002E TD01602006E TD.15A.05.T.E. TD.15A.05.T.E.