Tr a n s f er Switches
Magnum-Based Designs
Catalog Number Selection
Using the Catalog Numbering System provides an overview
of the 10 basic style/feature categories which generate the
15-digit catalog number.
Transfer Switch—Magnum Soft Load Transfer Switches 800–3200A
PCS = Power Case Switch
PCB = Power Circuit Breaker
Product Selection
Transfer Switch Catalog Number Identification
Transfer switch equipment
catalog numbers provide
a significant amount of
relevant information that
pertains to a particular piece
of equipment. The catalog
number identification table
provides the required
interpretation information.
An example for an open
transition switch is offered to
initially simplify the process.
Example: Catalog number
(circled numbers correspond
to position headings in the
table below.
The catalog number
CTVCMGE32000XRU
describes a Soft Load ATS
with the drawout switching
devices mounted vertically
in the enclosure. The
intelligence, represented
by the ATC-5000, is a
microprocessor-based
logic package.
The Magnum breaker is used
as the switching device and
is a three-pole molded case
breaker for each source.
The continuous current rating
of this equipment is 2000A
and is applicable at 480/277
Vac, 60 Hz. The transfer
switch equipment is enclosed
in a NEMA 3R enclosure and
is listed for Underwriters
Laboratories (UL).
Voltage
A = 120V, 60 Hz, three-phase, three-wire
B = 208/120V, 60 Hz, three-phase, four-wire
E = 600V, 60 Hz, three-phase, three-wire
E = 600V, 60 Hz, three-phase, four-wire
G = 220/127V, 50 Hz, three-phase, four-wire
G = 220/110V, 50/60 Hz, single-phase, three-wire
H = 380/220V, 50 Hz, three-phase, four-wire
K = 600V, 50 Hz, three-phase, four-wire
M = 230V, 50 Hz, three-phase, three-wire
M = 230V, 50 Hz, single-phase, three-wire
N = 401/230V, 50 Hz, three-phase, four-wire
O = 415/240V, 50 Hz, three-phase, four-wire
W = 240/120V, 60 Hz, single-phase, three-wire
W = 240V, 60 Hz, three-phase, three-wire
W = 240/120V, 60 Hz, three-phase, four-wire hi-leg
W = 230/115V, 60 Hz, single-phase, three-wire
X = 480V, 60 Hz, three-phase, three-wire
X = 480/277V, 60 Hz, three-phase, four-wire
X = 480/240V, 50 Hz, single-phase, two-wire
Z = 346/220V, 50 Hz, three-phase, four-wire
Logic
C = ATC-5000
Orientation
V = Vertical
Type
CT = Closed
transition
Frame
MG = Molded cases
Magnum DS
Poles
3 = Three-pole
4 = Four-pole
Switch
A = Fixed mount, power case
switch PCS both
B = Fixed mount, power case
circuit breaker
PCB both
C = Fixed mount, pcb
normal, PCS emergency
D = Fixed mount, PCS
normal, PCB emergency
E = Drawout, PCS both
F = Drawout, PCB both
G = Drawout, PCB normal,
PCS emergency
H = Drawout, PCS normal,
PCB emergency
Amperes
0800 = 800A
1000 = 1000A
1200 = 1200A
1600 = 1600A
2000 = 2000A
2500 = 2500A
3200 = 3200A
Listing
U = UL listed
Enclosure
S = NEMA 1
R = NEMA 3R
CT V C MG E 3 2000 X R U
VC MG E 3 2000 X
3 4 5 6 7 8 9to
12 13
to