Tr a n s f er Switches
Magnum-Based Designs
Approximate Dimensions in Inches (mm)
Magnum 4000–5000A Units
Note: The typical Magnum ATS at 4000 and 5000A ratings will include one cubicle with the Source 1 and Source 2 power case switches or breakers.
A second cubicle called a wireway is most likely required unless bus is used for the connections per Connection Type table above. Cable connections
to the wireway cubicle can be made from the top or bottom. The wireway cubicle will have removable panels on the front, and cable connections
may be made from the top or the bottom. Cable connections to the power case switch or breaker cubicle are made from the back. Consult factory
for dimensions. The wireway width is 32.00 inches (812.8 mm).
Front View With Covers
B
C
Front View Without Covers
Right Side View
A
Wireway Cubicle ATS Cubicle
Source 1
(Normal)
Source 2
(Emergency)
SP
Emergency Lugs —
Located in Rear of Cubicle
Normal
Lugs
Load
Lugs
Wireway
Cubicle
SP = Shipping Split.
Consult factory for dimensions.
Connection Type (4000–5000A Only)
Connection Type
WirewayLine Emergency Load
Cable Cable Cable Yes
Bus Cable Cable Yes
Cable Bus Cable Yes
Cable Cable Bus Yes
Bus Bus Cable No
Bus Cable Bus No
Cable Bus Bus No
Bus Bus Bus No