Tr a n s f er Switches
Breaker-Based Designs
Standards and Certifications
Complies with UL 1008 and UL 489 standards
IBC seismic qualified
Meets American Bureau of Shipping (ABS) approval
Catalog Number Selection
Non-Automatic Breaker-Based Transfer Switch
Technical Data and Specifications
Wallmount Transfer Switch Standard Terminal Data for
Power Cable Connections
Transfer Switch Ratings—Systems Coordination
Information—Withstand, Closing and Interrupting Ratings
Notes
All terminals suitable for copper or aluminum conductors. For alternate terminal sizes,
contact Eaton.
For maximum breaker ratings in circuits when the transfer switch is evaluated as a
“Motor Branch Circuit Conductor,” refer to NEC Section 430-25 for sizing.
Class RK5 fuse with 100 kA rating.
Four-pole units rated 35 kA.
Type
NT = Non-automatic
Orientation
H = Horizontal
V = Vertical
Logic
E = Electro-mechanical
Enclosure
K = Open
S = NEMA 1
R = NEMA 3R
J = NEMA 12
L = NEMA 4
D = NEMA 4X
Certification
U = UL 1008 listed
R = UL recognized
X = No listing
NT H E KD C 2 0100 W S U
Mounting
Fixed
A = FM, N (MCS), E (MCS)
B = FM, N (MCB), E (MCB)
C = FM, N (MCB), E (MCS)
D = FM, N (MCS), E (MCB)
Number of Poles
2 = Two-pole
3 = Three-pole
4 = Four-pole
Frame
Molded case device
FD = 30–150A
KD = 150–300A
LD = 400–600A
MD = 600–800A
ND = 800–1000A
Amperes
0030 = 30A
0070 = 70A
0100 = 100A
0150 = 150A
0225 = 225A
0300 = 300A
0400 = 400A
0600 = 600A
0800 = 800A
1000 = 1000A
Voltage
A = 120V, 60 Hz
B = 208V, 60 Hz
E = 600V, 60 Hz
G = 220V, 50/60 Hz
H = 380V, 50 Hz
K = 600V, 50 Hz
M = 230V, 50 Hz
N = 401V, 50 Hz
O = 415V, 50 Hz
W = 240V, 60 Hz
X = 480V, 60 Hz
Z = 365V, 50 Hz
Switch
Ampere Rating
Breaker
Frame
Line Side (Normal
and Standby Source)
Load
Connection
Neutral
Connection
30–100 HFD (1) #14–1/0 (1) #14–1/0 (3) #14–1/0
150–225 HFD (1) #6–300 (1) #6–300 (3) #4–300
225–300 HKD (1) #3–350 (1) #6–350 (3) #4–350
400 HLD (1) 4/0–600 (2) #1–500 (6) 250–350
600 HLD (1) 3/0–350 (2) #1–500 (6) 250–350
600 HMDL (2) #1–500 (2) #1–500 (12) 4/0–500
600 (four-pole) NB (3) 3/0–400 (3) 3/0–400 (3) 3/0–400
800 HMDL (3) 3/0–400 (3) 3/0–400 (12) 4/0–500
800 HNB (4) 4/0–500 (4) 4/0–500 (12) 4/0–500
1000 HNB (4) 4/0–500 (4) 4/0–500 (12) 4/0–500
Standard UL 1008 Three-Cycle—Horizontal and Vertical Industrial
ATS
Ampere
Rating
Any Breaker Rating Ratings When Used with Upstream Fuse (kA)
240V 480V 600V
Maximum
Fuse Rating
Fuse
Type
600V
30 100 65 25 200 J, T 200
70 100 65 25 200 J, T 200
100 100 65 25 200 J, T 200
150 100 65 25 400 J, T 200
200 100 65 25 400 J, T 200
225 100 65 25 400 J, T 200
300 100 65 25 400 J, T 200
400 100 65 25 600 J, T 200
600 100 65
25 800/1200 J, T 100/200
800 65 50
25 1200/1600 L 100/200
1000 65 50
25 1600 L 200