Specifications
Distribution Products Catalog CA08101001E—October 2010 www.eaton.com 27
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16.3
Tr a n s f er Switches
Breaker-Based Design
Manual Switch with Door Closed—
Must Open Door to Engage the
Manual Handle
Manual Transfer Switch Shown
Without Deadfront
Standards and Certifications
●
Complies with UL 1008
and UL 489 standards
●
IBC seismic qualified
●
Meets American Bureau of
Shipping (ABS) approval
Catalog Number Selection
Manual Breaker-Based Transfer Switch
Note
Horizontal is available only on ratings 150A or less.
MT H X MD C 2 0100 E S U
Type
MT = Manual
Orientation
H = Horizontal
V = Vertical
Logic
X = No logic
Mounting (Fixed)
A = FM, N (MCS), E (MCS)
B = FM, N (MCB), E (MCB)
C = FM, N (MCB), E (MCS)
D = FM, N (MCS), E (MCB)
Number of Poles
2 = Two-pole
3 = Three-pole
4 = Four-pole
Amperes
0030 = 30A
0070 = 70A
0100 = 100A
0150 = 150A
0225 = 225A
0300 = 300A
0400 = 400A
0600 = 600A
0800 = 800A
1000 = 1000A
Voltage
E = 600V, 60 Hz
Enclosure
K = Open
S = NEMA 1
J = NEMA 12
R = NEMA 3R
L = NEMA 4
D = NEMA 4X
Certification
U = UL 1008 listed
Frame
Molded case device
FD = 30–150A
KD = 150–300A
LD = 400–600A
MD = 600–800A
ND = 800–1000A