Tr a n s f er Switches
Standard and Optional Features
Transient Voltage Surge
Suppression
Eaton’s Clipper Power
System —Visor™ series
transient voltage surge
suppression (TVSS)
components can be
integrated into any closed
transition soft load switch.
Surge current ratings 100 kA,
160 kA and 200 kA per phase
provide a range of cost-
effective
facility-wide
protection solutions. Status
indication on each phase is
standard with any TVSS
option. Metering and
communication capabilities
are also available. See
Appendix C for details.
Communications
Optional communication
capability via Communication
Gateway is available, allowing
remote data access, control,
programming, system
interface and dispatch.
System Interface
A system control panel
provides a user-friendly
interface to the closed
transition soft load controller,
allowing operators to easily
monitor the switching
devices position and manually
test
the generator and the
system operations.
Switching Devices
Status Lights
●
Source 1 open (green)
●
Source 1 closed (red)
●
Source 1 trip (amber)
●
Source 2 open (green)
●
Source 2 closed (red)
●
Source 2 trip (amber)
Front Panel Control Switches
and Lights
The combination of the
following pilot devices can be
implemented on the unit:
●
AUTO/TEST switch
●
SYSTEM TEST switch
●
TEST MODE switch
●
ALARM SILENCE switch
●
READY FOR OPERATION
lamp (white)
—verifies the
ATC-5000 status
Optional Intergral Overcurrent
Protection Capability
For service entrance
applications, Digitrip
microprocessor-based trip
units can be integrated into
the power switching devices.
This eliminates the need for
the separate upstream
protective device, saving
installation cost and space.
Available with various
combinations of long, short,
instantaneous and ground
fault protection, Digitrips
can communicate with
Eaton’s IMPACC and
PowerNet Power
Management Systems.
Optional On-Board 24 Vdc
Power Supply
On-board 24 Vdc power
supply circuit, consisting of
two 12 Vdc gel-cell UPS type
batteries and battery charger,
is available on the unit to
provide DC control power
to soft load transfer switch
components. Engine battery
can be connected in the
“best battery” circuit as
well, further improving the
system’s reliability.
Optional Components
Description
Service Entrance Rating
16N Overcurrent protection—normal
16E Overcurrent protection—emergency
16B Overcurrent protection—both
37A Service entrance
37B Service entrance with ground fault
Metering
18O IQ Analyzer—normal
18P IQ Analyzer—emergency
18Q IQ Analyzer—N/E selectable
18U IQ Analyzer—load
Plant Exerciser
23J Automatic 24 hours/7 days selectable load/no load
Expanded Controller I/O
25A Additional discrete and analog I/O for Genset control and monitoring
Space Heater and Thermostat
41C 400W heater with thermostat
Surge Protection
51M4B Engine control (24 Vdc) surge device
51NA1 100 kA surge device with AdVisor Source 1
51NS1 100 kA surge device with SuperVisor Source 1
51NN1 100 kA surge device with NetVisor Source 1
51QA1 160 kA surge device with AdVisor Source 1
51QS1 160 kA surge device with SuperVisor Source 1
51QN1 160 kA surge device with NetVisor Source 1
51SA1 200 kA surge device with AdVisor Source 1
51SS1 200 kA surge device with SuperVisor Source 1
51SN1 200 kA surge device with NetVisor Source 1
On-Board 24 Vdc Power Supply
24C Battery charger and gel-cell batteries
Protective Devices
53A Beckwith M-3410A
53B Schweitzer SEL-547
53C Basler BE1-951
53D Beckwith M-3520
53E Schweitzer SEL-351
53F Basler BE1-IPS100
Communication
54B External Communication Gateway
54C Serial Modbus Over Ethernet
Field Startup
56A 2-day startup (includes 1 day for travel)