16.2
Tr a n s f er Switches
Contactor-Based Designs
Catalog Number Selection
Automatic Transfer Switch
Technical Data and Specifications
UL 1008 Withstand and Close-On Ratings (kA)
UL 1008
Ampere
Rating
480V 480V 600V 600V Rating When Used with Upstream Fuse
Any
Breaker
Specific
Breaker
Any
Breaker
Specific
Breaker
Rating
(kA)
Test
Voltage Fuse Type
Maximum Fuse
Amperes
40 10 30 10 22 100 480 RK5 200
80 10 30 10 22 100 480 RK5 200
100 10 30 10 22 100 480 RK5 200
150 10 30 22 35 100 600 RK5 400
200 10 30 22 35 100 600 RK5 400
225 30 50 50 65 200 600 RK5 600
260 30 50 50 65 200 600 RK5 600
400 30 50 50 65 200 600 RK5 600
600 50 65 50 65 200 600 L, R, J, T 1600
800 50 65 50 65 200 600 L, R, J, T 1600
1000 50 65 50 65 200 600 L, R, J, T 1600
1200 50 65 50 65 200 600 L, R, J, T 1600
AT C 3 C2 X 3 0400 X S U
Type
AT = Automatic
NT = Non-automatic
Orientation
C = Contactor
Logic
1 = ATC-100
3 = ATC-300
8 = ATC-800
E = Electro-mechanical
Mechanism
C2 = 2-position
C3 = 3-position
Switch
X = Fix mount
Amperes
0040 = 40A
0080 = 80A
0100 = 100A
0150 = 150A
0200 = 200A
0225 = 225A
0260 = 260A
0400 = 400A
0600 = 600A
0800 = 800A
1000 = 1000A
1200 = 1200A
Voltage
A = 120V, 60 Hz
B = 208V, 60 Hz
E = 600V, 60 Hz
G = 220V, 50 Hz
H = 380V, 50 Hz
K = 600V, 50 Hz
M = 230V, 50 Hz
W = 240V, 60 Hz
X = 480V, 60 Hz
Z = 365V, 50 Hz
Enclosure
K = Open
S = NEMA 1
J = NEMA 12
R = NEMA 3R
Certification
U = UL listed
Number of
Poles
2 = Two-pole
3 = Three-pole
4 = Four-pole