Step 4 - Download the configuration file
1 Connect to the system controller with DCTools/Web. See details on page 46 in the
System Controller Operation Handbook.
2 If a copy of the old configuration file, or a master configuration file is available,
then use DCTools to restore (download) it to the new system controller.
See Backup and Restore on page 42 in the System Controller Operation Handbook.
If you receive an error message about the MIB file version, please contact your
Eaton dc product supplier for advice.
3 If a copy of the old configuration file, or a master configuration file is not
available, then use the keypad or DCTools/Web to change the configuration
settings to the correct values (provided the system controller is set for the correct
nominal system voltage).
Step 5 - Check the system controller operation
1 Map the I/O board (SC200 only):
In DCTools/Web go to: RXP.
Copy the I/O board serial number(s) from the RXP Devices table to the I/O
Board to Serial Number Mapping table to map an IOB Number to each I/O board
(overwrite an existing serial number if required).
If multiple SiteSure-3G modules are connected use the I/O board Identify function
to physically identify each module. See details in the System Controller Operation
Handbook.
2 Check that the system controller has registered all rectifiers.
3 Check all control processes, alarms and current measurement(s).
4 Check the power system identification parameters and communications settings.
5 Change the configuration file as required to ensure that the system controller
operates as intended.
6 Check the system controller time (SC200 only). See details in the System
Controller Operation Handbook.