Specifications
Maintenance
Copyright © 2007-2012 Eaton Corporation. All Rights Reserved.
IPN 997-00012-49F November 2012
57
Problem
Possible Cause
Required Action
LVD Status LED(s) (on I/O
board) are on.
LVD contactor is energized.
None, this is normal operation.
LVD Status LED(s) are off
(I/O board Power On LED is
on).
LVD contactor is de-energized.
None, this is normal operation.
LVD Status LED(s) flashing.
The contactor is in the wrong
state (SC200 or SC100 internal
state does not match signal from
contactor auxiliary switch).
Check the electrical and mechanical
operation of the contactor and auxiliary
switch.
Check all wiring and connectors. See
Connections on page 11.
LVD Type setting is incorrect.
Check LVD Type setting.
LVD contactor(s) not
operating.
LVD settings incorrect.
Check LVD is enabled and set to correct
values. See details in the System
Controller Operation Handbook.
Check that the LVD manual control is set
to AUTO. See details in the System
Controller Operation Handbook.
Check that the contactor is correctly
configured and mapped to the I/O
board. See details in the System
Controller Operation Handbook (SC200
only).
Contactor is disconnected.
Check the control and dc power cables
are connected. See details on page 11.










