To use a web browser for Restore (SC200 only)
1 Connect to the SC200 via a web browser. For details see Ethernet Communications in the
System Controller Operation Handbook.
2 Go to Tools.
3 Select Restore Tool.
4 Select the file type:
System Snapshot (*.dcs): Configuration file including site specific settings.
Configuration (*.dcc): Configuration file without site specific settings - Site Identity, IP
Address, S3P Address, battery characterization data).
Fragment (*.dcf): Restore part of a configuration file (such as battery characterization
data).
5 Click Next, and then select a file name to Restore a configuration.
Starting the SC200 or SC100
When dc power is applied to the SC200 or SC100 (via the RXP connector YS11) the start-up
sequence begins.
SC200
Approx.
120s
Start-up screen
Main screen
Menu screen
The values shown are
configurable, see details in the
System Controller Operation
Handbook. All active Critical,
Major, Minor and Warning
alarms are displayed.
See navigation details on page 81.
If Logon is required see Keypad
Access Security on page 44.
SC100
Approx
20s
Start-up screen
First status screen
Main menu
All active alarms are displayed.
See details on page 82.