Specifications
Commissioning
Copyright © 2007-2012 Eaton Corporation. All Rights Reserved.
IPN 997-00012-49F November 2012
101
Test
Test procedure
Adjustment
Fast Charge
For details see Fast Charge test in System Controls on page
96.
Battery Test
For details see Battery Test in System Controls on page 96.
In Discharge
Note 3
Connect load to the system.
Turn off the ac supply to the rectifiers.
Allow the battery to start discharging.
Ensure alarm operates.
Config Error
Note 4
Load incorrect configuration file.
- or -
Remove all rectifiers from the system.
Apply an incorrect external voltage to the system:
24V for a 48V system
48V for a 24V system
Ensure alarm operates.
User Assigned
Alarms
See User Digital Input test on page 102.
Battery Current
Limit
For details see Battery Current Limit test in System
Controls on page 96.
Rectifier No Load
Ensure the dc load and batteries are isolated from the
system.
Ensure alarm operates.
Rectifier Current
Limit
Apply a dc load to the system.
Turn off rectifiers until the remaining rectifiers reach the
Rectifier Current Limit threshold.
- or -
Set the Rectifier Current Limit slightly below the existing
rectifier current being delivered to the load.
Ensure alarm operates.
High Rectifier
Temperature
Note 5
Unable to test.
AC Phase 1/2/3 Fail
Note 6
Turn off ac phase 1 to the power system.
Ensure alarm operates.
Repeat for phase 2 and phase 3.
AC Phase 1/2/3
Voltage
Note 6
Reduce the High AC Threshold below the existing ac
voltage.
Ensure alarm operates.
Increase the Low AC Threshold above the existing ac
voltage.
Ensure alarm operates.
AC Frequency
Note 6
Change the Nominal AC Frequency setting.
Change the AC Frequency Threshold.
Ensure alarm operates.
Engine Run Option
Note 7
Change the state of the digital input with Engine Run
function.
Ensure alarm operates.