Specifications

Commissioning
Copyright © 2007-2012 Eaton Corporation. All Rights Reserved.
IPN 997-00012-49F November 2012
97
Test
Test procedure
Adjustment
Current Share
Note 6
View the individual rectifier currents with the SC200 or
SC100 or DCTools/Web.
Ensure the currents are all at 0 amps.
Connect load to the system.
Ensure that all rectifiers share the load evenly and any
variation is within specification.
None
Battery Test
Set the Battery Test Interval to 0 days.
Set the Battery Test Duration to 30 minutes
Set the Battery Test Termination Voltage to a value
approximately 2 volts below the float voltage.
Connect load to the system.
Start the Battery Test.
Ensure the SC200 or SC100 indicates that a Battery Test has
started.
Wait until the system voltage reduces below the Termination
Voltage.
Confirm the Battery Test fails.
Ensure the Battery Test Fail alarm is displayed on the SC200
or SC100.
Ensure the Battery Test stops and the system voltage returns
to the float voltage setting.
Clear the Battery Test Fail alarm in DCTools/Web.
Set the Battery Test Duration to 1 minute.
Set the Battery Test Termination Voltage to a value
approximately 10 volts below the float voltage.
Connect load to the system.
Start the Battery Test.
Ensure the SC200 or SC100 indicates that a Battery Test has
started.
Wait for the Battery Test Duration time to expire.
Confirm the Battery Test passes.
Ensure the Battery Test stops and the system voltage returns
to the float voltage setting.
Reset the Battery Test settings to the original values.
None
Low Voltage
Disconnect
Manual Operation
Note 7
Set the LVD manual control to CONNECT.
Ensure the LVD contactor is connected.
Ensure the SC200 or SC100 displays an LVD Manual alarm.
Ensure the I/O board LVD LED is on.
Set the LVD manual control to AUTO.
Ensure the SC200 or SC100 shows no LVD alarms.
Ensure the I/O board LVD LED is on.
Set the LVD manual control to DISCONNECT.
Ensure the LVD contactor disconnects.
Ensure the SC200 or SC100 displays an LVD Manual alarm.
Ensure the I/O board LVD LED is off.
Set the LVD manual control to AUTO.
Ensure the LVD connects.
Ensure the SC200 or SC100 shows no LVD alarms.
Ensure the I/O board LVD LED is on.
None
Low Voltage
Disconnect
Check the LVD contactor is connected.
Increase the LVD Disconnect Voltage Threshold.
None