Specifications
53
www.eaton.com/powerquality 1300 UPS UPS
Premier Modular High Efficiency UPS Solutions 200 - 1100kVA
UPS rating
kVA 200 225 275 300 400 450 550 600 825 1100
kW 180 202 250 240 360 405 500 480 750 1000
General characteristics
Efficiency Up to 95%
Parallel capability Up to 5 modules
Audible noise 75 to 81.5dBA @ 1m, model dependant
Altitude (max) 1000 m at 40°C
Internal N+1
redundance capable
Yes
Field upgradeable for redundancy
System bypass module Included
Input characteristics
Voltage 415
Voltage range +15% / -20%
Frequency range 45-65 Hz
Power factor 0.99
Input current distortion 3-5% in nominal load condition
Soft start capability Yes
Internal backfeed
Protection
Yes (except on 200/400kVA models)
Output characteristics
Voltage 415
Regulation ± 1%
Inverter PWM with IGBT switching
Voltage THD < 2% (100% linear load); < 5% (standard non-linear load)
Load power factor range 0.7 lagging to 0.8 leading
Battery
Battery types VRLA, AGM,
Battery voltage 480 V
Temperature
compensation
Optional
Charging method Advanced battery management technology
Dimensions (W x D x H)
Weights
200kVA
1350x880x1800 mm
810 kg
225,275 and 300kVA 1350x880x1880 mm 830 kg
400kVA and 200kVA redundant
1890x880x1880 mm
1390 kg
550/600kVA and 275/300kVA redundant 1890x880x1880 mm 1430 kg
550 kVA redundant 2520x880x1880 mm 2030 kg
275 kVA field upgrade UPS-U 740x880x1880 mm 600 kg
825 kVA 3710x880x1880 mm 3460 kg
1100 kVA 4450x880x1880 mm 3460 kg
User benefits
Control panel (LCD) 8 lines x 40 characters
Frequency conversion Optional
Remote display panel Optional
Buildings alarm inputs 2 (galvanic isolated)
Serviceability
Back/side against wall installation Standard
Optional accessories
Integrated maintenance bypass
Input breaker
Batteries in line-and-match cabinets
Certification
Safety IEC 62040.1.1
EMC EN50091.2
Communications
Software compatibility - Power Xpert
Communication cards - Two communication bays standard. Maximum of four
communication bays with the communication expansion option. The following
connectivity options can be installed at any time.
- ConnectUPS Web/SNMP/xHub, Modus card, Relay Interface Card (Use for
AS400s), Industrial Relay Card (5A@120V), Hot Sync
®
CAN Bridge Card provides CAN
communications, isolated RS-485 port, Environmental Monitoring Probe (EMP)
Eaton 9395 Technical Specifications
275 kVA field-upgradable
UPS-U can be added for
redundancy
550 kVA Integrated system bypass
module (ISBM)
Redundant 275 kVA
uninterruptible power system
Eaton 9395 UPS with redundant, field-installed module