General
UPS output power rating (1.0 p.f.) 30, 40, 50, 80, 100, 120, 150, 160, 200 kW
Efficiency in double conversion mode
Up to 97%
Efficiency in Energy Saver System (ESS)
> 99%
Field upgradeable Yes
Inverter/rectifier topology Transformer-free IGBT with PWM
Audible noise 30–50 kW: < 60 dBA, 80–200 kW: < 65 dBA, ESS operation: < 47 dBA
Altitude (max) 1000 m without derating (max 2000 m)
Input
Input wiring 3ph + N + PE
Nominal voltage rating (configurable) 220/380, 230/400, 240/415 V 50/60 Hz
Input voltage range High +20% rectifier input, 10% bypass input, Low –15% at 100% load, –40% at 50% load without battery discharge
Input frequency range 40–72 Hz
Input Power Factor 0.99
Input ITHD 30 kW: < 4.5%, 40–200 kW: < 3%
Soft start capability Yes
Internal backfeed protection Yes
Battery
Battery type VRLA
Charging method ABM technology or Float
Temperature compensation Optional
Battery nominal voltage (VRLA) 432 V (36 x 12 V, 216 cells) or 480 V (40 x 12 V, 240 cells)
Note: Strings with different battery voltage may not be paralleled!
Charging current maximum 30–50 kW 16.5 A, 80–100 kW 33 A, 120–150 kW 49.5 A, 160–200 kW 66 A
Battery start capability Yes
Output
Output wiring 3ph + N + PE
Nominal voltage rating (configurable) 220/380, 230/400, 240/415 V 50/60 Hz
Output UTHD < 1% (100% linear load)., < 5% (reference non-linear load)
Rated output power factor 1.0
Permitted load power factor 0.8 lagging – 0.8 leading
Overload on inverter 10 min 102–110%; 60 sec 111–125%; 10 sec 126–150% 300 ms > 150%. On battery mode 300 ms > 126%
Overload when bypass available Continuous < 125%, 10 ms 1000%
Note: Bypass fuses may limit the overload capability!
Accessories options
External battery cabinets with long-life batteries, External maintenance bypass switch, integrated manual bypass (up to 150kW) and MiniSlot connectivity
(Web/SNMP, ModBus/Jbus, Relay)
Communications
MiniSlot 3 communication bays
Network/SNMP interface Yes, standard
Serial ports Built-in host and device USB
Relay inputs/outputs 5 relay inputs and dedicated EPO 1 relay output
Environmental
Operating temperature 0ºC to +40ºC
Storage temperature -25ºC to +55ºC
Altitude 1000m without derating (Maximum 2000m)
Audible noise at 1 metre 55dB @ 75% Load, 60dB @ 100% Load
Compliance with standarts
Safety (CB certified) IEC 62040-1
EMC IEC 62040-2
Performance IEC 62040-3