Specifications

45
www.eaton.com/powerquality 1300 UPS UPS
Premier Three-phase UPS for servers and industrial applications
Eaton 9355 Technical Specifications
Rating 8kVA 10kVA 12kVA 15kVA 20kVA 30kVA 40kVA
Model 9355-8-N 9355-10-N 9355-12-N 9355-15-N 9355-20-N-MBS 9355-30-N-MBS 9355-40-N-MBS
Capacity (kVA/kilowatts) 8 / 7.2 10 / 9 12 / 10.8 15 / 13.5 20 / 18 30 / 27 40 / 36
Dimensions (mm) WxDxH 305 x 702 x 817 494 x 762 x 1684
With extra runtime 305 x 702 x 1214 -
Weight (kg)
UPS without batteries
UPS with internal 1xBAT
UPS with internal 2xBAT
UPS with internal 3xBAT
UPS with internal 4xBAT
75
165
N/A
N/A
75
165
275
N/A
N/A
75
165
275
N/A
N/A
75
165
275
N/A
N/A
200
300
400
500
600
200
N/A
400
500
600
217
N/A
N/A
517
617
Input Connection Hardwired Hardwired Hardwired Hardwired Hardwired Hardwired Hardwired
Output Connection Hardwired Hardwired Hardwired Hardwired Hardwired Hardwired Hardwired
*Typical runtime with 1xBAT
Typical runtime with 2xBAT
Typical runtime with 3xBAT
Typical runtime with 4xBAT
15 min
33 min
N/A
N/A
10 min
25 min
N/A
N/A
8 min
20 min
N/A
N/A
5 min
15 min
N/A
N/A
5 min
13 min
22 min
31 min
N/A
7 min
13 min
20 min
N/A
N/A
8 min
12 min
Operational
Nominal input voltage (Vac) 220/380, 230/400, 240/415 Vac three phase
Input voltage range 175/305V - 276/478V at 100% load, 115/200V - 276/478V at 50% load
Operating frequency 50/60 Hz (45 to 65 Hz)
Input power factor 0.99
Input current distortion 5% THD in normal network condition
Nominal output voltage 380/400/415 three phase
Output voltage regulation 2% static;
5% dynamic at 100% load change, < 1 ms response time
Overload capacity 150% for 5 sec / 125% for 1 min (online),
1000% for 5 msec (bypass)
Efficiency 92% with computer load; 93% with linear load
User interface
LCD-display Graphical LCD with blue backlight, English, German and Spanish languages, extendable
LED 4 LED for notice and alarm
Standard communication ports 1 x RS232 for local support, 2 x X-Slot (empty);
1 x relay contact, 1 x emergency power off input, 2 x environmental input
Optional External battery cabinets; isolation transformer; external mechanical bypass switch; X-Slot;
Web/SNMP, Modbus/Jbus, relay card, RS232 port, Hot Sync
®
card
Environmental
Operating temperature 0
o
C to +40
o
C
Storage temperature -15
o
C to +40
o
C
Altitude < 1000 m at +40
o
C, < 3000 m at +25
o
C
Audible noise at 1 metre < 50dBA at 1 metre
Certification
Quality ISO 9001; 2000 and ISO 14001: 1996
Markings CE and GOST markings / C-Tick
Safety IEC 62040-1-1, IEC 60950, EN 62040-1-1
EMC EN 50091-2 Class A, C-Tick