Specifications

43
www.eaton.com/powerquality 1300 UPS UPS
Essential 3 Phase protection for IT and Industrial applications
Description kVA Model description Part number Net weight (kg) Dimensions (WxDxH mm)
Standard models with
space for internal
batteries
20 Eaton E Series DX 20 kVA B
EDX20K4EB, EDX20K4AUB
120 420 x 710 x 1245
30 Eaton E Series DX 30 kVA B EDX30K4EB, EDX30K4AUB 195 470 x 710 x 1753
40 Eaton E Series DX 40 kVA B
EDX40K4EB, EDX40K4AUB
195 470 x 710 x 1753
Standard models with
internal batteries
installed
20 Eaton E Series DX 20 kVA BI EDX20K4EBI, EDX20K4AUBI 272
420 x 710 x 1245
30 Eaton E Series DX 30 kVA BI
EDX30K4EBI, EDX30K4AUBI
515 470 x 710 x 1753
40 Eaton E Series DX 40 kVA BI
EDX40K4EBI, EDX40K4AUBI
515 470 x 710 x 1753
Eaton E Series DX 3 Phase Technical specifications
Input Operating environment
Nominal Voltage
380/400/415 Vac (L-L) Temperature 0°C to 40°C
220/230/240 Vac (L-N) Humidity 20% to 90% non-condensing
Frequency 40-65 Hz (self-adaptive to 50 Hz and 60 Hz) Efficiency
Wiring 3-Phase + N + PE
Line mode
92%
THD i <5% HE mode (high
efficiency)
98%
Power factor
>0.99
Display
Dual-line input Supported LCD UPS status and operating instructions. Input voltage,
output voltage, current, frequency, charger voltage and
current, fault and warning display.
Battery
Type Maintenance free VRLA batteries
Backup time
Up to 15 min with internal batteries on 20-40kVA, more
with external batteries
LED UPS operation status
Battery Voltage 360 V (30x12 V, 180 cells), 20kVA
384 V (32x12 V, 192 cells), all other models
Warning equipment
Buzzer alarm and light double LED
Output
Communication interface
Voltage 380/400/415 Vac (L-L) 220/230/240 Vac (L-N) RS-232, AS/400, RS485, service, EPO, interface for
battery temperature sensor, intelligent communications
slot
Frequency 50/60 Hz
Phase Three-phase four wire + ground
Power factor 0.8
Overload capability 125% 10 minutes, 150% 1 minute
Runtime for 20-40kVA UPS with internal batteries p.f. 0.7 (typical IT server/computer load)
Battery Qty 20 30 40 kVA
7 Ah 12 V 2 x 30 6 min
9 Ah 12 V 2 x 30 10 min
7 Ah 12 V 3 x 32 6 min
9 Ah 12 V 3 x 32
10 min
7 Ah 12 V
4 x 32 11 6 min
9 Ah 12 V 4 x 32 15 10 min
Run time chart provides typical information. Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.