Specifications

37
www.eaton.com/powerquality 1300 UPS UPS
Premier series 9 power protection for medium to high density rack environments
Technical Specifications 6kVA 8kVA 11kVA
Rating (kVA/kW) 6kVA/5.4kW 8kVA/7.2kW 11kVA/10kW
Electrical Characteristics
Technology On-line double conversion with Power Factor Correction (PFC) system
Input voltage range 1:1 models: 176-276V without derating (up to 100–276V with derating)
3:1 models: 305V-480V without derating (up to 175V-480V with derating)
Output voltage/THDU 200/208/220/230/240V +/– 1%;
THDU <2% (1:1 & 3:1)
200/208/220/230/240/250V +/– 1%; THDU <2% (1:1 & 3:1)
Input frequency range/THDI 40-70Hz, 50/60Hz autoselection, frequency converter as standard, THDI < 5%
Efficiency Up to 94% in Online mode, 98% in Hi-Efficiency
mode
Up to 95% in Online mode, 98% in Hi-Efficiency mode
Crest factor/short circuit current 3:1/90A 3:1/120A 3:1/150A
Overload capacity 102–110% : 120s, 110–125%: 60s, 125–150%:
10s, >150%: 500ms
102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms
Connections
Input 1:1 Models Terminal block (up to 10 mm²) Terminal block (up to 16mm²)
Input 3:1 Models Terminal block (up to 16mm²)
Output 1:1 Models Terminal block + 2 controlled groups of 4 IEC
C13 (10A) + 2 IEC C19 (16A)
Terminal block
Output 3:1 Models Terminal block
Output with optional HotSwap Maintenance Bypass 1:1 Models Terminal block + 3 IEC C13 (10A) + 2 IEC C19
(16A)
Terminal block + 4 IEC C19 (16A)
Output with optional HotSwap Maintenance Bypass 3:1 Models Terminal block + 4 IEC C19 (16A)
Batteries (1:1 Models)
Typical backup times at 50 and 70% load*
9PX (8 & 11 kVA = 1 Power Module + 1 EBM) 11/8 min 20/15 min 13/9min
9PX + 1 EBM (8 & 11 kVA = Total 2 EBM) 48/34 min 48/32 min 32/21 min
9PX + 4 EBM (8 & 11 kVA = Total 5 EBM) 170/120 min 140/100 min 100/70 min
Batteries (3:1 Models)
Typical backup times at 50 and 70% load*
9PX (6, 8 & 11kVA = 1 Power Module + 1 EBM)
30/20min 20/15 min 13/9min
9PX + 1EBM (total 2 EBM)
70/45min 48/32 min 32/21 min
9PX + 4 EBM (total 5 EBM)
210/140 min 140/100 min 100/70 min
Battery management ABM
®
and temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic
recognition of external battery units.
Communication
Communication ports 1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for
remote On/Off and 1 for Remote Power Off, 1 DB15 for parallel operation.
Communication slot 1 slot for Network-MS card, ModBus-MS or Relay-MS cards.
Operating conditions, standards and approvals
Operating temperature 0 to 40°C continuous
Noise level <45dB (1:1) / 48dB(3:1) <48dB (1:1 & 3:1) <50dB (1:1 & 3:1)
Safety IEC/EN 62040-1, UL 1778 (1:1), CSA 22.2
EMC, performance IEC/EN 62040 -2 , FCC Class A (1:1), IEC/EN 62040-3 (Performance)
Approvals CE, CB report (TUV), UL (1:1), C-Tick
Dimensions H x W x D/Weight
UPS 440(19’’)*130(3U)*685mm/48kg (1:1)
440(19’’)*260(6U)*700mm/88kg (3:1)
440(19’’)*260(6U)*700mm/84kg (1:1)
440(19’’)*260(6U)*700mm/88kg (3:1)
440(19’’)*260(6U)*700mm/86kg (1:1)
440(19’’)*260(6U)*700mm/88kg (3:1)
EBM 440(19’’)*130(3U)*645mm/68kg (1:1)
440(19’’)*130(3U)*680mm/65kg (3:1)
440(19’’)*130(3U)*680mm/65kg 440(19’’)*130(3U)*680mm/65kg
Power module 440(19’’)*130(3U)*700mm/23kg (3:1 only) 440(19’’)*130(3U)*700mm/19kg (1:1)
440(19’’)*130(3U)*700mm/23kg (3:1)
440(19’’)*130(3U)*700mm/21kg (1:1)
440(19’’)*130(3U)*700mm/23kg (3:1)
Customer Service and Support
Warranty 3 years electronics, 2 years battery
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc
Part Numbers 9PX 6kVA 9PX 8kVA 9PX 11kVA
UPS 1:1 = 9PX6Ki
Power Module 3:1 = 9PX6Ki31PM 1:1 = 9PX8KiPM, 3:1 = 9PX8Ki31PM 1:1 = 9PX11KiPM , 3:1 = 9PX11ki31PM
EBM 1:1 = 9PXEBM180, 3:1 = 9PXEBM240 9PXEBM240 9PXEBM240
HotSwap Maintenance Bypass 1:1 = MBP6Ki, 3:1 = MBP11Ki31 1:1 = MBP11Ki, 3:1 = MBP11Ki31 1:1 = MBP11Ki, 3:1 = MBP11Ki31
Transformer Module (Single Phase in/out) TFMR11Ki TFMR11Ki TFMR11Ki
Supercharger with Rack Kit 1:1 = N/A, 3:1 = SC240RT SC240RT SC240RT
1.8m Battery Connection Cable 1:1 = EBMCBL180, 3:1 = EBMCBL240 EBMCBL240 EBMCBL240
Battery Integration System BINTSYS BINTSYS BINTSYS
Rack Kit 9RK 9RK 9RK