Specifications

35
www.eaton.com/powerquality 1300 UPS UPS
Premier series 9 protection for medium density rack environments
Technical Specifications 5kVA 6kVA
Rating (kVA/kW) 5kVA/4.5kW 6kVA/5.4kW
Electrical Characteristics
Technology On-line double conversion with Power Factor Correction (PFC) system
Nominal voltage 200/208/220/230/240V
Input voltage range 176-276V without derating (up to 100–276V with derating)
Output voltage/THDU 200/208/220/230/240V +/– 1%; THDU <2%
Input frequency range/THDI 40-70Hz, 50/60Hz autoselection, frequency converter as standard, THDI < 5%
Efficiency
Crest factor/short circuit current 3:1/90A 3:1/90A
Overload capacity 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 500ms
Connections
Input Terminal block (up to 10 mm²)
Outputs Terminal block + 2 controlled groups of 4 IEC C13 (10A) + 2 IEC C19 (16A)
Batteries
Typical backup times at 50 and 70% load*
9SX 13/10 min 11/8 min
9SX + 1 EBM 60/40 min 48/34 min
9SX + 4 EBM 220/150 min 170/120 min
Battery management ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection,
automatic recognition of external battery units.
Communication
Communication ports 1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal
block for remote On/Off and 1 for remote power Off.
Communication slot 1 slot for Network-MS card, ModBus-MS, Relay-MS, or Industrial Relay cards.
Operating conditions, standards and approvals
Operating temperature 0 to 40°C continuous
Noise level <45dB <45dB
Safety IEC/EN 62040-1, UL 1778, CSA 22.2
EMC, performance IEC/EN 62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance)
Approvals CE, CB report (TUV), UL, C-Tick
Dimensions H x W x D/Weight
UPS 440(19’’)*130(3U)*685mm/48kg 440(19’’)*130(3U)*685mm/48kg
EBM 440(19’’)*130(3U)*645mm/68kg 440(19’’)*130(3U)*645mm/68kg
Customer Service and Support
Warranty 2 years warranty
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc
Part Numbers 9SX 5kVA 9SX 6kVA
UPS
UPS with Rack Kit 9SX5KiRT 9SX6KiRT
EBM
EBM with Rack Kit 9SXEBM180RT 9SXEBM180RT
Power Module
HotSwap Maintenance ByPass MBP6Ki MBP6Ki
Transformer Module TFMR11Ki TFMR11Ki
Supercharger with Rack Kit
1.8m Battery Connection Cable EBMCBL180 EBMCBL180
Battery Integration System BINTSYS BINTSYS