Specifications
35
www.eaton.com/powerquality 1300 UPS UPS
Premier series 9 protection for medium density rack environments
Technical Specifications 5kVA 6kVA
Rating (kVA/kW) 5kVA/4.5kW 6kVA/5.4kW
Electrical Characteristics
Technology On-line double conversion with Power Factor Correction (PFC) system
Nominal voltage 200/208/220/230/240V
Input voltage range 176-276V without derating (up to 100–276V with derating)
Output voltage/THDU 200/208/220/230/240V +/– 1%; THDU <2%
Input frequency range/THDI 40-70Hz, 50/60Hz autoselection, frequency converter as standard, THDI < 5%
Efficiency
Crest factor/short circuit current 3:1/90A 3:1/90A
Overload capacity 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 500ms
Connections
Input Terminal block (up to 10 mm²)
Outputs Terminal block + 2 controlled groups of 4 IEC C13 (10A) + 2 IEC C19 (16A)
Batteries
Typical backup times at 50 and 70% load*
9SX 13/10 min 11/8 min
9SX + 1 EBM 60/40 min 48/34 min
9SX + 4 EBM 220/150 min 170/120 min
Battery management ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection,
automatic recognition of external battery units.
Communication
Communication ports 1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal
block for remote On/Off and 1 for remote power Off.
Communication slot 1 slot for Network-MS card, ModBus-MS, Relay-MS, or Industrial Relay cards.
Operating conditions, standards and approvals
Operating temperature 0 to 40°C continuous
Noise level <45dB <45dB
Safety IEC/EN 62040-1, UL 1778, CSA 22.2
EMC, performance IEC/EN 62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance)
Approvals CE, CB report (TUV), UL, C-Tick
Dimensions H x W x D/Weight
UPS 440(19’’)*130(3U)*685mm/48kg 440(19’’)*130(3U)*685mm/48kg
EBM 440(19’’)*130(3U)*645mm/68kg 440(19’’)*130(3U)*645mm/68kg
Customer Service and Support
Warranty 2 years warranty
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc
Part Numbers 9SX 5kVA 9SX 6kVA
UPS – –
UPS with Rack Kit 9SX5KiRT 9SX6KiRT
EBM – –
EBM with Rack Kit 9SXEBM180RT 9SXEBM180RT
Power Module – –
HotSwap Maintenance ByPass MBP6Ki MBP6Ki
Transformer Module TFMR11Ki TFMR11Ki
Supercharger with Rack Kit – –
1.8m Battery Connection Cable EBMCBL180 EBMCBL180
Battery Integration System BINTSYS BINTSYS