Specifications
31
www.eaton.com/powerquality 1300 UPS UPS
Premier series 9 Tower UPS for all critical applications
Eaton 9130 Tower Technical Specifications
Rating
700VA 1000VA 1500VA 2000VA 3000VA 6000VA
Part number PW9130G700T-XLAU PW9130G1000T-XLAU PW9130G1500T-XLAU PW9130G2000T-XLAU PW9130G3000T-XLAU PW9130G6000T-XLAU
Capacity (VA/Watts) 700/630 1000/900 1500/1350 2000/1800 3000/2700 6000/5400
Dimensions WxDxH (mm) 160x355x250 160x383x250 160x435x250 214x410x345 214x410x345 242x542x575
Weight (kg) 12.2 14.5 19.0 34.5 34.5 75.5
Input connection IEC C14-10A IEC C14-10A IEC C14-10A IEC C14-10A IEC C20-16A Hard Wired
Output connection (4) AUST 10A (4) AUST 10A (4) AUST 10A (5) AUST 10A
(1) IEC C13-10A
(5) AUST 15A
(1) IEC C19-16A
Hard Wired
Operational
Nominal input voltage
(Vac)
240Vac (200/208/220/230 selectable)
Input voltage range 700-1500VA: 120/140/160-276 Vac (at 33%/66%/100% 0.7pf load)
2000-3000VA: 140/160/180-276 Vac (at 33%/66%/100% 0.7pf load)
6000VA: 120/140/160/180-276V (25%/50%/75%//100% 0.9pf Load)
Operating frequency 50/60 Hz auto sensing, tolerance 40-70Hz
Input power factor 0.99
Nominal output voltage 240Vac (200/208/220/230 selectable)
Output voltage regulation +/-2%
Overload capacity 700-3000VA: Up to 130 % for 12 seconds, 130-150% for 2 sec
6000VA: Up to 130 % for 120 seconds, 130-150% for 30 sec
Efficiency 700-2000VA: 90% online, 93% High Efficiency Mode
3000VA: 91% online, 93% High Efficiency Mode
6000VA: 95% online, 98% High Efficiency Mode
User interface
LCD display LCD display showing both UPS meters and UPS settings
LED Four LEDs; UPS On, UPS on Battery, UPS on bypass, Alarm
Standard communication
ports
RS232 and USB as standard on all models
Optional 1 Mini Slot for Network Card-MS, Relay Card-MS or Network & Modbus Card-MS connectivity cards
Environmental
Operating temperature 0ºC – +40ºC
Storage temperature -15ºC – +40ºC
Altitude < 3000 m
Audible noise at 1 metre 700-3000VA: < 52 dBA, 6000VA: < 55 dBA
Certification
Markings C-Tick, CE, GS
EMC EN62040-2 Emissions, category C1; Immunity, category C2
Battery Runtimes (in minutes) Standard Extended Battery Modules
Load (VA/Watts) % 0f Load Internal Batteries w/1 EBM w/2 EBM w/3 EBM w/4 EBM
PW9130G700T
700/630 100% 5 N/A N/A N/A N/A
350/315 50% 14 N/A N/A N/A N/A
PW9130G1000T-XLAU
1000/900 100% 6 31 51 82 100
500/450 50% 19 68 111 192 246
PW9130G1500T-XLAU
1500/1350 100% 5 24 46 69 90
750/675 50% 14 61 112 172 221
PW9130G2000T-XLAU
2000/1800 100% 11 44 79 115 162
1000/900 50% 28 96 168 258 336
PW9130G3000T-XLAU
3000/2700 100% 6 21 51 66 93
1500/1350 50% 15 60 100 169 215
PW9130G6000T-XLAU
6000/5400 100% 6 33 64 96 130
3000/2700 50% 19 78 148 211 266
Run time chart provides typical information. Battery runtimes are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Longer run times available with Extended Battery Cabinets. Please consult your sales representative for information.