Specifications
29
www.eaton.com/powerquality 1300 UPS UPS
Superior series 9 protection for critical applications
LCD Multilingual display
- 6 languages,
- displays measurements,
- displays alarms,
- access to control and set-up
menus.
Panel for batteries replacement
(Hot swappable)
1 x USB port + 1 x serial port +
remote ON/OFF and emergency stop
inputs.
EXB battery unit connector.
EXB units recognised automatically.
8 x IEC 10A sockets, including 4 x
Powershare programmable sockets
and 1 x IEC 16A socket.
Mini Slot connectivity card slot.
Mountings for HotSwap MBP and
FlexPDU.
Eaton EX Technical Specifications 1000 RT2U 1500 RT2U 2200 3000 - 3000 XL
Rating (VA/W) 1000 VA / 900 W
(1)
1500 VA / 1350 W
(1)
2200 VA / 1980 W 3000 VA / 2700 W
(1)
Format RT2U (tower/rack 2U) RT2U (tower / rack 2U) and RT3U (tower / rack 3U)
Electrical characteristics
Architecture
On-line double conversion with automatic by-pass and power factor correction
Input voltage and frequency ranges without using
batteries
100/120/140/160 V(2) to 284V - 40 to 70 Hz
100/120/160/184 V(2) to 284V - 40 to 70 Hz
Output voltage and frequency 230 V (adjustable to 200/208/220/240/250 V), 50/60 Hz auto-
select or frequency converter mode (3)
230 V (adjustable to 200/208/220/240 V),
50/60 Hz auto-select or frequency converter mode
Connections
Input
1 x IEC C14 (10A) socket
1 x IEC C20 (16A) or terminal block on HotSwap
MBP HW (Hard-Wired)
Outputs
6 x IEC C13 (10A) sockets
8 x IEC C13 (10A) sockets + 1 x IEC C19 (16A) socket
Remotely controlled Powershare sockets
2 independent groups: 2 + 1 x IEC C13 (10A) sockets
2 groups of 2 x IEC C13 (10A) on Eaton EX
Additional outputs with HotSwap MBP
4 x Aust 3 pin or 6 x IEC 10A sockets or terminal blocks (HW version)
Additional outputs with FlexPDU
6 x Aust 3 pin or 12 x IEC 10A sockets
Battery
Typical backup times for 50 and 70% load
(6)
except for Eaton EX 3000 XL
(5)
EX 18 min / 12 min 13 min / 9 min 17 min / 12 min 15 min / 10 min
EX + 1 EXB 75 min / 50 min 50 min / 35 min 85 min / 60 min 60 min / 40 min
EX + 4 EXB 250 min / 200 min 180 min / 120 min 285 min / 200 min 190 min / 150 min
Battery management
Automatic weekly test (period adjustable using LCD display or in software supplied), automatic recognition of external
battery units => continuous maximisation of backup time + deep discharge protection
Interfaces
Indicators and display
3 x LEDS + adjustable multilingual display: display of measurements, access to control and set-up menus
Communication ports
1 x USB port + 1 x RS232 serial port and relay contacts (4) + 1 x mini terminal block for remote ON/OFF and emergency stop
Communications card slots
1 x Mini Slot for Network Card-MS, Relay Card-MS or Network & Modbus Card-MS connectivity cards
Operating conditions, standards and approvals
Operating temperature noise level
0°C to 40°C continuous, 45 dBA
Performance - Safety - EMC
IEC/EN 62 040-3 (VFI-SS-113), IEC/EN 62 040-1-1, IEC/EN 60 950-1 (RD), IEC/EN 62 040-2 C1 Class
Approvals CE, TüV GS, CB report, cTüV-US CE, TüV, CB Report, UL CE, TüV, CB Report, UL
Dimensions (H x W x D) / Weight
EX RT3U - - 131 x 440 x 490 mm
(7)
/ 30 kg (3000 XL = 18 kg)
EX RT2U 86.5 x 438 x 483 mm / 25kg 86.5 x 438 x 483 mm / 27kg 86 x 440 x 640 mm / 31 kg
EX EXB RT3U (excludes rack kit) - 131 x 440 x 490 mm
(7)
/ 42kg
EX EXB RT2U 86.5 x 438 x 483 mm / 24.5 kg - -
Customer Service & Support
2 years warranty Standard product exchange, including the battery
Warranty+ Optional 3-years warranty (depending on the country please visit www.eaton.com/powerquality)
1: Maximum rating with EXB battery units: Eaton EX 1000 = 800 W, Eaton EX 1500 =1200 W and Eaton EX 3000=2400W. 2: Lower limits for <20%, <33%, <66%, >=66% of nominal power (VA). For active
output power greater than 0.7 and 0.8 nominal rating, the lower limit is 180V and 190V respectively. 3: Derated by 15% when used as a frequency converter. 4: USB and RS232 serial ports cannot be used
simultaneously. 5: Except Eaton EX 3000 XL: UPS with high speed charger, without built-in batteries, for custom configurations: ask us for details. 6: Runtimes are shown at 0.7 power factor. Backup times are
approximate and may vary with equipment, configuration, battery age, temperature, etc. 7: compatible with 600 mm deep rack.
Part Numbers
1000 1500
2200 3000
EX RT3U (excludes rack kit) - - M68400 M68402 - XL: M68404
EX RT2U (includes rack kit)
M68182 M68184 M68401 M68403
EX EXB M68186 (includes rack kit) M68186 (includes rack kit) M68405 M68405
EX Rack Kit 2U/3U - - M68441 M68441
Eaton EX