Specifications
25
www.eaton.com/powerquality 1300 UPS UPS
Premier efficient & manageable protection for high-end IT applications
Graphical LCD display :
- Clear information on UPS status and measurements
- Enhanced configuration capabilities
- Available in 7 languages
Panel for batteries replacement (Hot swappable)
1 USB port + 1 serial port + remote ON/OFF and remote
power OFF inputs
External battery (EBM) connector
8 IEC 10A + 1 IEC 16A sockets with energy metering
(including 4 programmable sockets)
Mini Slot for connectivity cards
Eaton 5PX 3000i RT2U
Eaton 5PX Technical Specifications
1500 2000 2200
3000
Rating (VA/W) 1500VA / 1350W 2000VA / 1800W 2200VA / 1980W 3000VA / 2700W
Format RT2U (rack / tower 2U) RT2U (rack / tower 2U) RT2U (rack / tower 2U) RT2U & RT3U
Electrical characteristics
Technology Line-Interactive High Frequency (Pure Sinewave, Booster + Fader)
Input voltage and frequency ranges 160V-294V (adjustable to 150V-294V) 47 to 70 Hz (50 Hz system),
without using batteries 56.5 to 70 Hz (60 Hz system), 40 Hz in low-sensitivity mode
Output voltage and frequency 230 V (+6/-10 %) (Adjustable to 200V / 208V / 220V / 230V / 240V), 50/60 Hz +/- 0.1 % (autosensing)
Connections
Input 1 IEC C14 (10 A) socket 1 IEC C14 (10 A) socket 1 IEC C20 (16 A) socket 1 IEC C20 (16 A) socket
Outputs 8 IEC C13 (10 A) 8 IEC C13 (10 A) sockets 8 IEC C13 (10 A) sockets,
1 IEC C19 (16 A) socket
8 IEC C13 (10 A) sockets,
1 IEC C19 (16 A) socket
Remotely controlled sockets 2 groups of 2 x IEC C13 (10 A)
Additional outputs with Hot Swap MBP 4 AUS 10A + 1 IEC 16A sockets or 6 IEC 10 A sockets or terminal blocks (HW version)
Additional outputs with FlexPDU 6 AUS 10A + 1 IEC 16A sockets or 12 IEC 10 A sockets
Batteries Typical backup times for 50 and 70% load*
5PX 19/11 mins 16/8 mins 15/8 mins 14/9 mins
5PX + 1 EBM 90/54 mins 66/39 mins 60/35 mins 66/38 mins
5PX + 4 EBM 285/180 mins 231/138 mins 210/125 mins 213/131 mins
Battery management ABM
®
& Temperature compensated charging method (user selectable), Automatic battery test, deep discharge
protection, automatic recognition of external battery units
Interfaces
Communication ports 1 USB port + 1 RS232 serial port and relay contacts (USB and RS232 ports cannot be used simultaneously)
+ 1 mini terminal block for remote ON/OFF and Remote Power Off
Communications card slots 1 Mini Slot for Network Card-MS, Relay Card-MS and Network & Modbus Card-MS connectivity cards
Operating conditions, standards and approvals
Operating temperature 0 to 40°C
Noise Level < 45 dBA < 45 dBA < 45 dBA < 50 dBA
Performance - Safety - EMC IEC/EN 62040-1-1 (Safety), IEC/EN 62040-2 (EMC), IEC/EN 62040-3 (Performance), C-Tick
Approvals CE, CB report, TÜV
Dimensions W x D x H / Weight
UPS Dimensions (mm) 441 x 522 x 86.2 (2U) mm 441 x 522 x 86.2 (2U) mm 441 x 522 x 86.2 (2U) mm 441 x 647 x 86.2 (RT2U) mm
441 x 497 x 130.7 (RT3U) mm
UPS Weight (kg) 27.6 kg 28.5 kg 28.5 kg 38.08 (RT2U), 37.33 (RT3U)
Dimensions of EBM same as UPS
Weight of the EBM 32.8 kg 32.8 kg 32.8 kg 46.4kg (RT2U), 44.4kg
(RT3U)
Customer Service & Support
Warranty 3 years on electronics, 2 years on batteries
* Runtimes are shown at 0.7 power factor. Backup times are approximate and may vary with equipment, configuration, battery age, temperature, etc.
Part Numbers 1500 2000 2200 3000 (RT3U) 3000 (RT2U)
UPS 5PX1500iRT 5PX2000iRT 5PX2200iRT2UAU 5PX3000iRT3UAU 5PX3000iRT2UAU
EBM 5PXEBM48RT 5PXEBM48RT 5PXEBM48RT 5PXEBM72RT3U 5PXEBM72RT2U