Datasheet
10/26/2017 091078 - HPL-ED2017 V37.0 EN 1 / 6
Main�switch,�2�pole,�20�A,�Emergency-Stop�function,�90�°,�Lockable�in�the
0�(Off)�position,�flush�mounting
Part�no. T0-1-102/EA/SVB
Catalog�No. 091078
EL-Nummer
(Norway)
1417106
Delivery�program
Product range Main switch
maintenance switch
Repair switch
Part group reference T0
Stop Function Emergency switching off function
With red rotary handle and yellow locking ring
Number of poles 2 pole
Locking facility Lockable in the 0 (Off) position
Degree of Protection Front IP65
Design flush mounting
Contact sequence
Switching angle ° 90
Function
Motor�rating�AC-23A,�50�-�60�Hz
400 V P kW 5.5
Rated uninterrupted current I
u
A 20
Number of contact units contact
unit(s)
1
Technical�data
General
Standards IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA, UL
Switch-disconnector according to IEC/EN 60947-3
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
Open °C -25 - +50
Enclosed °C -25 - +40
Overvoltage category/pollution degree III/3
Rated impulse withstand voltage U
imp
V AC 6000
Mechanical shock resistance g 15
Mounting position As required
Protection against direct contact when actuated from front (EN 50274) Finger and back-of-hand proof