Specifications

Qty Description
2 Powerware 150kVA Power Distribution Unit
Transformer Rating: 150kVA, k20, 150°C Rise, TP1
Cable Entry/Exit: Top or Bottom
Distribution: (4) 225A Subfeed Breakers
Monitoring: Eaton Subfeed Circuit Monitoring
Communications: Power Xpert Gateway Card (SNMP, ModBus, TCP/IP)
Features: Air Skirt
Heat Rejection: 18,460 Btu/Hr
PDU Dimensions: 39" Wide, 35" Deep, 80" High
PDU Weight: 2,782 Pounds
Embedded Warranty/Service Plan: Full 1-Year including parts, labor, and expenses
6 Powerware Remote Power Panel
Number of Inputs: (2) via Main Input Lugs (450A)
Cable Entry/Exit: Top or Bottom
Panelboard Type: 42-Pole Cutler Hammer with 225A Main Breaker (80% Rated, 35kAIC)
Panelboard Qty: (2) Front, (2) Rear
Branch Circuit Breakers: (5) 2P30A 10kAIC per side
RPP Dimensions: 24" Wide, 24" Deep, 80" High
RPP Weight: ~900 Pounds
4 FieldServer PDU ModBus - BACnet Converter
Transfers ModBus input values to BACnet protocol
4 Powerware PDU Certified Factory Test Data
Includes factory engineer certified written report from standard manufacturer factory test procedure.
1 Powerware PDU & RPP Startup 7x24
Includes startup for (4) PDU's and (6) RPP's
Performed by factory trained technician during overtime (non weekend) hours (M-F 5pm -8am).
1 Freight to VA/DC/MD
Dock to dock, FOB factory
1 FOB Destination
Legal ownership of equipment to take place at freight destination.
Specification Notes:
Proposal is based on Eaton's standard offering for UPS's in conjunction with the following project documents and with
comments as outlined below.
- Specification 262600 dated 12/10/13
- Specification 263353 dated 02/13/14
- Drawing E1.101 dated 02/13/14
262600-1.5.C - PDU's and RPP's are not seismic certified.
262600-2.1.B - Sound level tests results will be provided from sample production units. Sound level testing will not be
conducted on actual project equpment.
262600-3.3.D - PDU's will be tested to manufacturer's standard procedures in lieu of NETA prodecures.
262600-3.3.F - IR Scanning will not be performed.
263353-2.2.L - The unit shall operate with up to 110% of resistive/inductive load for 10 minutes, up to 125% for 30 seconds,
and up to 150% for 10 seconds.
263353-2.3.G - UPS is non-upgradeable.
263353-2.10 - Proposed UPS does not include output distribution section.
263353-2.16.B - Factory witness testing and travel for (1) owner's representative is included in base price.