Specifications

Qty Description
1 Eaton Power Xpert 9395 Certified Factory Test Data
Includes factory engineer certified written report from standard manufacturer factory test procedure.
1 Cutler Hammer 1200A Maintenance Bypass Panel
Current Capacity: 1200A
Interruption Capacity: 100kAIC
Configuration: 2-Breaker (MIS, MBP)
Trips: DigiTrip 310+ LS
Interlock: Electrical & Kirk Key with SKRU
Aux Contacts: 2A/2B
Features: (1) 1200AF/1000AT Load Bank Breaker
MBP Dimensions: 45" Wide, 24" Deep, 90" High
MBP Weight: 1200 Pounds
1 Enersys 16HX550 VRLA Battery Module
Link Voltage: 480VDC
Cabinets per UPS (4) at 32" Wide and 5,310 Pounds Each
Total Runtime: 6 minutes at 825kVA load
Disconnect: 600A DC Breaker internal to cabinet
Battery Module Dim: 128" Wide, 31.5" Deep, 84" High
Battery Module Weight: 21,240 Pounds
Note: DC cabling from cabinet to UPS or external disconnect provided by others.
1 Eaton Flex UPS Service Plan Year 2
Emergency Coverage: 7x24
On-Site Response Time: 8-Hours
Total Service Coverage Duration: 2-Years from startup
1 Eaton Cellwatch Battery Monitoring System
Provides detailed battery health report to individual cell level.
Installation: Included during normal working hours, M-F 8am-5pm.
Installation does not include wall penetrations, conduit, or 120VAC protected power.
1 Eaton Power Xpert 9395 Factory Witness Testing
Customer witnessed UPS factory testing.
Manufacturer's standard procedure only.
Includes food, travel, & lodging for (1) representative.
Performed during normal working hours. M-F 8am-5pm.
1 Custom Site Load Test
Site load testing performed with Resistive Load Bank with 100' Cable
Includes 30 minute functional test followed by 3.5 hour burn-in
Test performed during normal working hours only.
1 Technician Laptop
To be stored at site.
1 Freight to VA/DC/MD
Dock to dock
1 FOB Destination
Legal ownership of equipment to take place at freight destination.
PDU's & RPP's
2 Powerware 50kVA Power Distribution Unit
Transformer Rating: 50kVA, k20, 150°C Rise, TP1
Cable Entry/Exit: Top or Bottom
Distribution: (6) 60A Subfeed Breakers
Monitoring: Eaton Subfeed Circuit Monitoring
Communications: Power Xpert Gateway Card (SNMP, ModBus, TCP/IP)
Features: Air Skirt
Heat Rejection: 6,892 Btu/Hr
PDU Dimensions: 39" Wide, 35" Deep, 80" High
PDU Weight: ~1,864 Pounds
Embedded Warranty/Service Plan: Full 1-Year including parts, labor, and expenses