Table 3‐15. Power Cable Conduit Requirements (continued)
Number of
Conduits
Minimum Conduit
Trade Size
Number of Wires
in Conduit
TerminalVoltageUPS Model
Eaton 9395-825/825
400 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 5
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4 2
3
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5 3 5
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4 2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5 3 5
DC
Battery
(Positive, Negative, Ground)
See Note 1
Eaton 9395-825/450
Eaton 9395-825/500
Eaton 9395-825/550
See Note 2
400 Vac
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4 2
3
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5 3 5
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4 3 4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4 2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4 3 4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5 3 5
DC
Battery
(Positive, Negative, Ground)
See Note 1
NOTE 1 Select conduit taking into consideration the DC input wire sizes listed in Table 3‐4 on page 3-14, Table 3‐5 on page 3-15, Table 3‐6 on page 3-16
and Table 3‐7 on page 3-17 the DC terminations listed in Table 3‐11 on page 3-20, type of battery installation, and requirements from NEC Table 4,
Electrical Metallic Tubing (EMT).
NOTE 2 Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, these conduit sizes are specified for an
825kVA UPS.
NOTE 3 Bypass conduit data is not applicable to IOM configurations.
Table 3‐15. Power Cable Conduit Requirements
Eaton 9395-825
/
82
5
AC In
p
ut to UPS Rectifie
r
4
3
4
(
A
,
B
,
C
,
Ground
)
4
80
Vac
AC In
p
ut to B
yp
ass and Out
p
ut
(
Four Wire
)
4
3
4
(
A, B, C, Ground
)
B
atter
y
D
C
S
ee Note
1
(
Positive, Ne
g
ative, Ground
)