Specifications
UPS INSTALLATION PLAN AND UNPACKING
Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual 164201725 Rev 4 www.eaton.com/powerquality
3-21
Table 3‐12. Supplied External Wiring Terminal Hardware Kit
Part Size Quantity Terminals Used On Eaton Part Number
Bolt, Grade 5 M10 x 25 mm 15 Ground 180190078-087
Bolt, Grade 5 M12 x 45 mm 92
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180190078-113
Flat Washer M10 15 Ground 180500036-100
Flat Washer M12 184
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180500036-120
Conical Washer M10 15 Ground 180500037-100
Conical Washer M12 92
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180500037-120
Nut M12 92
Rectifier Input, Bypass Input, Battery Input,
Output, and Neutral
180200001-07
NOTE Bypass terminations are not applicable to IOM configurations.
Table 3‐13. Recommended Installation Parts and Tools (Not Supplied by Eaton)
Part Size Quantity Manufacturer Part Number Notes
Long Barrel 2‐Hole Lug
2/0 AWG
As required
Thomas & Betts 54862BE
Copper wire only
3/0 AWG Thomas & Betts 54864BE
4/0 AWG Thomas & Betts 54866BE
250 MCM Thomas & Betts 54868BE
300 MCM Thomas & Betts 54870BE
350 MCM Thomas & Betts 54872BE
400 MCM Thomas & Betts 54874BE
500 MCM Thomas & Betts 54876BE
Manual Hydraulic Crimp Tool 14 Ton 1 Thomas & Betts TBM14M
Die Set N/A 1 Thomas & Betts 15506
Table 3‐14. Separate Rectifier Input UPM Power Cable Terminations for the Three UPM Eaton 9395-825/650, 9395-825/750, and 9395-825/825 and
the Two UPM Eaton 9395-825/450, 9395-825/500, 9395-825/550
Terminal Function Terminal Function Size of Pressure Termination
Tightening Torque
Nm (lb ft)
Type Screw
AC Input to each UPM Rectifier
E1 Phase A 2 - #6-250 kcmil
42.4 (375)
5/16” Hex
E2 Phase B 2 - #6-250 kcmil
42.4 (375)
5/16” Hex
E3 Phase C 2 - #6-250 kcmil
42.4 (375)
5/16” Hex
Table 3‐12.
S
u
pp
lied External Wiring Terminal Hardware Kit
Table 3‐13. Recommended Installation Parts and Tools (Not Supplied by Eaton
)