Specifications

UPS INSTALLATION PLAN AND UNPACKING
Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual 164201725 Rev 4 www.eaton.com/powerquality
3-14
Table 3‐4. Input/Output Ratings and External Wiring Requirements for the Three UPM Eaton 9395-825/650, 9395-825/750, and 9395-825/825
– Common Battery
Basic Unit Rating
Units Rating 50/60 Hz
kVA
kW
650
592
650
592
750
683
750
683
825
751
825
751
Input and Output Voltage Volts 400/400 480/480 400/400 480/480 400/400 480/480
AC Input to UPS Rectifier (0.98 Minimum pF)
Full load current plus battery recharge current
(3) Phases, (1) Ground
A
Amps 1079 891 1245 1028 1369 1130
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(4)
500
(3)
500
(4)
500
(4)
500
(5)
500
(4)
AC Input to UPS Bypass (Four Wire)
Full Load Current
(3) Phases, (1) Ground
B
Amps 938 782 1083 902 1191 992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
350
(3)
500
(4)
500
(3)
500
(4)
500
(4)
AC Input to UPS Bypass (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
B
Amps 938 782 1083 902 1191 992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
400
(4)
500
(3)
500
(5)
500
(4)
500
(5)
500
(5)
DC Input from Battery Disconnect to UPS
(1) Positive, (1) Negative
C
Total Amps 1280 1280 1502 1502 1600 1600
Minimum Conductor Size
Number per Pole
AWG or kcmil
(each)
350
(6)
350
(6)
500
(6)
500
(6)
500
(6)
500
(6)
AC Output to Critical Load (Four Wire)
Full Load Current
(3) Phases, (1) Ground
D
Amps 938 782 1083 902 1191 992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
500
(3)
350
(3)
500
(4)
500
(3)
500
(4)
500
(4)
AC Output to Critical Load (Five Wire)
Full Load Current
(3) Phases, (1) Neutral, (1) Ground
D
Amps 938 782 1083 902 1191 992
Minimum Conductor Size
Number per Phase
AWG or kcmil
(each)
400
(4)
500
(3)
500
(5)
500
(4)
500
(5)
500
(5)
Neutral Bonding Jumper (Four Wire Output Only)
Minimum Conductor Size
Number
AWG or kcmil
(each)
4/0
(1
4/0
(1)
4/0
(1
4/0
(1)
4/0
(1
4/0
(1)
NOTE Callout letters A, B, C, and D map to Figure 6‐5 , Figure 6‐7, Figure 6‐9, Figure 6‐11, or Figure 6‐15. Callout letters A, C, and D map to
Figure 6‐17 or Figure 6‐19.
NOTE Bypass wiring data is not applicable to IOM configurations.
Table 3‐4. In
p
ut/
O
ut
p
ut Ratings and External Wiring Re
q
uirements for the Three UPM Eaton 9395-825/650, 9395-825/750, and 9395-
8
25/82
5
C
ommon Batter
y
825
7
51
480/48
0
11
30
500
(4)
992
500
(
4
)
400
Each Battery Disconnect to UPS
(2)
500
DC Input from
E
AC In
p
ut to UPS By
p
ass
(
Four Wire
)
AC In
p
ut to UPS Rectifier (0.98 Minimum
p
F
)
A
B
C
AC Output to Critical Load (Four Wire)
D
992
500
(
4
)
Neutral Bonding Jumper (Four Wire Output Only)
4
/0
(
1
)