Specifications

Installation Reference
A-32 Eaton PDU (150 kVA) Installation and Operation Manual 164202126—Rev 5 www.eaton.com/powerquality
as
as
Table O. Eaton 150 kVA PDU Input Power Cable Terminations (415V)
Terminal Function Rating (kVA)
Main Breaker
Rating
Terminal Function
Number and Size of
Pressure Termination
Tightening Torque
Nm (lb in)
Type and Size
Screw
AC Input to Main
Breaker CB1 (and CB2,
if installed)
50 90A A (Black) Phase A 1 – #14 – 1/0 #14–10:
#8:
#6–#4:
#3–1/0:
4 (35)
4.5 (40
5.1 (45)
5/6 (50)
Slotted
B (Red) Phase B 1 – #14 – 1/0 Slotted
C (Blue) Phase C 1 – #14 – 1/0 Slotted
75 150A A (Black) Phase A 1 – #4–4/0 13.5 (120) 5/16” Hex
B (Red) Phase B 1 – #4–4/0 13.5 (120) 5/16” Hex
C (Blue Phase C 1 – #4–4/0 13.5 (120) 5/16” Hex
100 200A A (Black) Phase A 1 – #4–4/0 13.5 (120) 5/16” Hex
B (Red) Phase B 1 – #4–4/0 13.5 (120) 5/16” Hex
C (Blue Phase C 1 – #4–4/0 13.5 (120) 5/16” Hex
125 250A A (Black) Phase A 1 – #4–4/0 13.5 (120) 5/16” Hex
B (Red) Phase B 1 – #4–4/0 13.5 (120) 5/16” Hex
C (Blue Phase C 1 – #4–4/0 13.5 (120) 5/16” Hex
150 300A A (Black) Phase A 2 – 2/0–250 kcmil 31 (275) 5/16” Hex
B (Red) Phase B 2 – 2/0–250 kcmil 31 (275) 5/16” Hex
C (Blue Phase C 2 – 2/0–250 kcmil 31 (275) 5/16” Hex
Customer Ground All All G (Green) Ground 2 – #14 – 1/0 5.6 (50) 5/16” Hex
Table P. Eaton 150 kVA PDU Input Power Cable Terminations (480V)
Terminal Function Rating (kVA)
Main Breaker
Rating
Terminal Function
Number and Size of
Pressure Termination
Tightening Torque
Nm (lb in)
Type and Size
Screw
AC Input to Main
Breaker CB1 (and CB2,
if installed)
50 80A A (Black) Phase A 1 – #14–1/0 #14–10:
#8:
#6–#4:
#3–1/0:
4 (35)
4.5 (40
5.1 (45)
5/6 (50)
Slotted
B (Red) Phase B 1 – #14–1/0 Slotted
C (Blue) Phase C 1 – #14–1/0 Slotted
75 125A A (Black) Phase A 1 – #4–4/0 13.5 (120) 5/16” Hex
B (Red) Phase B 1 – #4–4/0 13.5 (120) 5/16” Hex
C (Blue Phase C 1 – #4–4/0 13.5 (120) 5/16” Hex
100 150A A (Black) Phase A 1 – #4–4/0 13.5 (120) 5/16” Hex
B (Red) Phase B 1 – #4–4/0 13.5 (120) 5/16” Hex
C (Blue Phase C 1 – #4–4/0 13.5 (120) 5/16” Hex
125 200A A (Black) Phase A 1 – #4–4/0 13.5 (120) 5/16” Hex
B (Red) Phase B 1 – #4–4/0 13.5 (120) 5/16” Hex
C (Blue Phase C 1 – #4–4/0 13.5 (120) 5/16” Hex
150 225A A (Black) Phase A 2 – 2/0–250 kcmil 31 (275) 5/16” Hex
B (Red) Phase B 2 – 2/0–250 kcmil 31 (275) 5/16” Hex
C (Blue Phase C 2 – 2/0–250 kcmil 31 (275) 5/16” Hex
Customer Ground All All G (Green) Ground 2 – #14–1/0 5.6 (50) 5/16” Hex
as
Table P. Eaton 150 kVA PDU Input Power Cable Terminations
(
480V
)
A
C
Input to Main
Breaker CB1 (
Customer Ground
All
All
G (Green)
Gr
ound
2 – #14–1/0
5.6 (50)
5/16” Hex
150
225A
A (Black)
Phase A
2 – 2/0–250 kcmil
31 (275)
5/16” Hex
B (Red)
Phase B
2 – 2/0–250 kcmil
31 (275)
5/16” Hex
C (Blue
Phase C
2 – 2/0–250 kcmil
31 (275)
5/16” Hex