Specifications
Installation Reference
A-2 Eaton PDU (150 kVA) Installation and Operation Manual 164202126—Rev 5 www.eaton.com/powerquality
5. The recommended clearances around the PDU cabinet are shown in Table C. The clearances specified
allow the doors on the cabinets to open a full 180°.
6. The basic environmental requirements for PDU operation are:
- Ambient Temperature Range: 0–40°C (32–104°F)
- Recommended Operating Range: 20–25°C (68–77°F)
- Maximum Relative Humidity: 95%, noncondensing
Table B. Equipment Weight – Front Service Access PDUs
Component
Rating
kVA
Maximum Weight kg (lb)
Shipping Installed Point Loading
PDU 150 1207 (2662) 1170 (2580) 4 at 293 (645)
PDU with single front-facing sidecar 150 1478 (3258) 1423 (3137) 4 at 356 (784)
PDU with single side-facing sidecar 150 1399 (3084) 1357 (2992) 4 at 339 (748)
PDU with dual front-facing sidecar 150 1748 (3854) 1676 (3694) 4 at 419 924)
PDU with dual side-facing sidecar 150 1590 (3506) 1544 (3404) 4 at 386 (851)
PDU with single front-facing sidecar
and single side-facing sidecar
150 1669 (3680) 1610 (3549) 4 at 403 (887)
PDU with dual input sidecar N/A N/A N/A N/A
PDU with dual input sidecar
and single front-facing sidecar
150 1686 (3718) 1614 (3558) 4 at 404 (890)
PDU with dual input sidecar and
single side-facing sidecar
150 1608 (3554) 1548 (3413) 4 at 387 (853)
Table C. PDU Cabinet Clearances
From the Top of the Cabinet Minimum 457.2 mm (18") for ventilation
From the Front of the Cabinet 914.4 mm (36") working space
From the Back of the Cabinet
(if side access is available)
Minimum 101.6 mm (4") for ventilation
508 mm (20") for side-facing sidecar door clearance
From the Back of the Cabinet
(front only service access PDU)
Minimum 101.6 mm (4") for ventilation
508 mm (20") for side-facing sidecar door clearance
From the Back of the Cabinet
(if side access is not available)
Minimum 914.4 mm (36") for working space
From the Right or Left Side of the Cabinet
(PDU only, no sidecars)
Minimum 914.4 mm (36") from one side for working space or rear access
508 mm (20") for door clearance
From the Right or Left Side of the Cabinet
(PDU and front-facing sidecars)
Minimum 914.4 mm (36") from one side for working space or rear access
610mm (24") for door clearance
From the Right or Left Side of the Cabinet
(PDU and side-facing sidecars)
Minimum 914.4 mm (36") for working space or rear access
Table
C
. PD
U
C
abinet
C
learance
s
F
rom the Top of the Cabine
t
M
inimum 457.2 mm (18
"
) for ventilatio
n
F
rom t
h
e
F
ront of the
C
abinet
9
14.4 mm (36") working spac
e
F
rom the Back of the
C
abine
t
M
inimum 101.6 mm (4"
)
for ventilation
508 mm
(
20"
)
for side-facin
g
s
id
ecar
d
oor c
l
earance
(if side access is available
)
F
rom the Back of the
C
abine
t
M
inimum 914.4 mm (36") for working space
(if side access is not available)
F
rom the Ri
g
ht or Le
f
t
S
ide of the
C
abinet Minimum 914.4 mm
(
36"
)
from one side
f
or workin
g
space or rear access
508 mm
(
20"
)
for door clearance
(PD
U
only, no sidecars)