A-70 Eaton PDU (150 kVA) Installation and Operation Manual 164202126—Rev 5 www.eaton.com/powerquality
A.10 Optional Air Skirt
An air skirt can be installed around the perimeter of the PDU Main Unit and any sidecars installed with the PDU.
An air skirt helps contain air flow under the PDU. See Figure A-63 through Figure A-68 for air skirt installation
illustrations.
CAUTION
Use air skirts only when the PDU is installed on a raised floor where the raised floor acts as a
plenum and provides adequate air flow to the PDU. The side skirts are to keep forced air from
escaping, but will block air if installed on a concrete or similar non-raised flat floor. Inadequate air
flow will cause the PDU to overheat
Figure A-63. 150 kVA PDU Main Unit with Optional Air Skirt Installed (Front and Side View)
Side ViewFront View