Specifications

5
EATON Power Xpert 9395 UPS Eaton.com/9395
Easy Capacity Test
The 9395 has the unique ability to test its entire power train
under full load stress without the requirement of an external load.
With no load connected, the 9395 is able to test all its power-
handling components, including the rectifier, inverter, contactors,
fuses, power busses, cabling, batteries, bypass (static switch),
magnetics, and filter capacitors. The net result of this innovative
load test is that there are no load banks to rent, no temporary load
connections to make, and no wasted energy. Furthermore, the
9395 has the ability to test the upstream bypass input breaker
")"THERECTIlERINPUTBREAKER2)"ANDALLTHEELECTRICALCABLES
between them. This load test feature can take the place of most
traditional load bank tests to save you time and money during
startup and commissioning. Eaton field technicians are trained to
use this load testing capability during a startup service to ensure
optimum calibration, maximum efficiency and inherent redundancy.
UTILITY FACILITY 9395 UPS
INVERTER
BATTERY
STATIC SWITCH
RECTIFIER
AC
DC
DC
AC
5
%
Scalable, redundant architecture meets current
and future requirements
The 9395 combines the reliability and redundancy of a multi-
module UPS into an integrated, pre-wired solution. With a unique,
mEXIBLEDESIGNTHATPROVIDESSCALABILITYTHE503CANADAPTTOFUTURE
changes in load demands and new requirements for higher
reliability without requiring the purchase of an additional UPS. For
EXAMPLETHE503ENABLESYOUTOADDAK6!50-INTHE
lELDFOR.REDUNDANCYORCAPACITY
275 kVA UPM275 kVA UPM275 kVA UPM825 kVA ISBM275 kVA UPM
9395 825 kVA
Easy Capacity Test Power Flow
As a result, they can produce a report that verifies these tests and
the overall performance of the UPS. All preventive maintenance
visits included with PowerTrust Service Plans for the 9395 include
this unique load testing feature to ensure that the UPS is operating
OPTIMALLY)TALSOVALIDATESTHEPERFORMANCEOFANINSTALLED503AND
can simulate various operations and power transfers.